Set up
Gas fitting settings
Natural gas settings
Natural gas L / H
RENDAMAX 30
Gas connection
pressure
mbar 20
CO
2
max. 65/85/120
%
8,8
r
0,2
CO
2
min. 65/85/120
%
8,2
r
0,2
Min. And max. CO
2
values must
always have a difference of 0.3%.
CO
2
max. 100
%
9,4
r
0,2
CO
2
min. 100
%
8,8
r
0,2
Setting the combustion quality
x
Connect the device to the water,
gas
and
electricity
Because of the different ignition be-
haviours of natural gas LL and natural
gas E, the gas-air compound must be
adjusted.
x
After successful ignition, the
prescribed
CO
2
value at full load
can be set by turning the control
screw (2) on the gas valve.
x
Set the CO
2
value for low load by
turning the control screw (1) on the
gas
fitting
1
Natural gas – liquid gas conversion
The following diaphragms must be
used for conversion to operation with
liquid gas (included with the delivery as
a set):
R30
65:
6,0 mm
R30
85:
6,0 mm
R30
100:
6,8 mm
R30
120:
8,0 mm
Liquid gas settings
Liquid gas
RENDAMAX 30
Gas connection
pressure
mbar 50
CO
2
max. 65/85/120
%
9,8
r
0,2
CO
2
min. 65/85/120
%
9,0
r
0,2
Min. And max. CO
2
values must
always have a difference of 0.3%.
CO
2
max. 100
%
10,4
r
0,2
CO
2
min. 100
%
9,6
r
0,2
2
19