Set up
Control measures
Circulating pump
The boiler is fitted with a pump
switch as standard. The pump
is activated when the boiler is
switched on. The pump con-
tinues to operate for a few
minutes after the burner
switches off. This period can
be adjusted. The standard
period is 2 minutes.
Type
'
t 20K
Pump data
Nominal
through-
flow
Boiler
resis-
tance
Pump type WILO Pump
setting
Feed
amount
at Q
Residual
feed
amount
at Q
Max.
power con-
sumption*
m
3
/h kPa
kPa kPa
W
R30/65
2,57
20
RS 25/7 PWM 3/C
max.
49
29
132
R30/85
3,38
25
RS 25/7 PWM 3/C
max.
40
15
132
R30/100
3,78
28
TOP-S
30/7
*** 3 52
24 195
R30/120
4,70
30
TOP-S
30/7
*** 3 42
12 195
*) Maximum pump power consumption stated in pump position 3
***) Pump optional
Water throughflow speed and pump data R30