50
Outdoor Setup
Unit Dimensions AEROTOP T.. Outdoor Setup
50
AEROTOP T..
AEROTOP T..
Min. 1200 mm
Min. 800mm
4
5
AEROTOP T20-T35
AEROTOP T07-T16
AEROTOP T für Aussenaufstellung
AEROTOP T
Width
Height without
protective roof
Depth
Depth for
ASS
Height
at bottom
Height without
protective roof
on top
Setup
foundation
Feet
A B C
C+
d e
AS
CS
q
T07
995
1513
650
1450
575
910
1095
750
28
T10
1095
1563
750
1650
575
960
1195
850
28
T12, T14, T16
1195
1663
750
1750
575
1060
1295
850
28
T20, T26
1195
1690
880
1980
670
975
1295
980
45
T32, T35
1295
1900
1000
2200
670
1185
1395
1100
45
Minimum clearances for service works
Prevent air short circuits
Attention: a setup in the frontage corner leads to a
higher noise emission and should be avoided,
if possible!
1 Flow line heater ø 1” (ø 11/4” from T20)
Hydraulic and electrical connections all at the
bottom
2 Return line heater ø 1” (ø 11/4” from T20)
3 Condensation water drain ø 3/4”
4 Air
inlet
5 Air
outlet
6 Electrical
connections
a Electric line low voltage
b Electric line safety low voltage
7 Vibration dampening rubber feet
8 Protective roof with distance spacer
9 Setup foundation, minimum height 300 mm,
account for local snow heights.
AEROTOP T..Outdoor setup :
Incl. Hoods for Air In / Air Out, protective roof and
regulating wall housing.
The air discharge can’t be set directly on a wall. In
this case a minimum distance of 2 meters must be
respected.
The air suction and discharge must not be oriented
as the windflow. The correct functioning could be
compromised by the wind action.
Summary of Contents for AEROTOP T Series
Page 87: ...Notes 87...