Configuration of Pressure Expansion Vessels
VN = VA x F x X
Key
Vn
= Expansion
volume
VA
=
System content acc. to
list
below
F
=
Temperature-dependent
Factor
40°C 50°C 60°C 80°C
0,0079 0,0121 0,0171 0,029
TZ = Average system temperature
TZ = (TV + TR)/2
= F
Up to 30 kW
X = 3,0
31 - 150 kW
X = 2,0
above 150 kW
X = 1,5
Safety factor for boiler output
X
= Safety factor
Important
Water contents of hot water tanks
(buffer storage) are not considered in
the table and must be added
separately.
1 = Floor heating
2 = Radiators
3 = Heating panels
Select the expansion vessel based on
the expansion volume and the system
height Hp. The system height Hp is the
height from the middle of the expansion
vessel up to the upper point of the
heating unit.
Type
0,5 bar
0,8 bar
1,0 bar
1,2 bar
1,5 bar
1,8 bar
PND 18
10,3
8,7
7,7 6,6 5,1 3,5
PND
25 14,3 12,0 10,7 9,1 7,1 4,7
PND
35 20,2 17,0 15,0 13,0 10,0 7,0
PND
50 28,6 24,4 21,4 18,5 14,3 9,8
PND
80 45,7 38,6 34,3 29,7 22,9 16,5
max. height Hp
2 m
5 m
7 m
9 m
12 m
15 m
Initial Pressure in Empty Vessel (= Hp + 0,3 bar)