15 ETS
®
Communication Objects list
CO
number
Object name
Conditions
Size
Flags
DPT
1
Slave input - Slave motion
Device type = Master
1 bit
C-W--
[1.017] Trigger
2
Slave output - Slave motion
Device type = Slave
1 bit
CR-T-
[1.001] Switch
3
Test output
Device type = Master
1 bit
CR-T-
[1.001] Switch
4
Measured lux value output
Device type = Master
2 bytes
CR-T-
[7.013]
Brightness [Lux]
5
C1 Manual Input
Device type = Master
External Switch = Yes
Light Control Output C1
= enabled
1 bit
C-W--
[1.001] Switch
6
C2 Manual Input
Device type = Master
External Switch = Yes
Light Control Output C2
= enabled
1 bit
C-W--
[1.001] Switch
7
C3 Manual Input
Device type = Master
External Switch = Yes
HVAC Output C3 =
enabled
1 bit
C-W--
[1.001] Switch
8
C4 Manual Input
Device type = Master
External Switch = Yes
HVAC Output C4 =
enabled
1 bit
C-W--
[1.001] Switch
9
C1 Light Control Output
Device type = Master
Light Control Output C1
= enabled
1 bit
CR-T-
[1.001] Switch
10
C1 Light Control Dimming
value
Device type = Master
Light Control Output C1
= enabled
1 byte
CR-T-
[5.001]
Percentage
(0..100%)
11
C1 Constant Light Control
Device type = Master
Light Control Output C1
= enabled
4 bit
CR-T-
[3.007]
Dimming control
12
C2 Light Control Output
Device type = Master
Light Control Output C2
= enabled
1 bit
CR-T-
[1.001] Switch
13
C2 Light Control Dimming
value
Device type = Master
Light Control Output C2
= enabled
1 byte
CR-T-
[5.001]
Percentage
(0..100%)
14
C2 Constant Light Control
Device type = Master
Light Control Output C2
= enabled
4 bit
CR-T-
[3.007]
Dimming control
15
C3 HVAC Control Output
Device type = Master
HVAC Output
C3 =
enabled
1 bit
CR-T-
[1.001] Switch
16
C4 HVAC Control Output
Device type = Master
1 bit
CR-T-