Figure 20 - HVAC control output C3 / C4 parameters
Parameter name
Conditions
Values [Default]
Auto / Semi-auto select
Device type = Master
Auto
Semi-auto
The automatic mode controls both switch-on and switch-off; the semi-automatic mode only controls
switch-off after a manual switch-on through the external control pushbutton.
HVAC switch-'ON' delay
Device type = Master
0...30 min
[1 min]
Sets the delay before the output is switched ON whenever a movement is detected; this is required to
prevent immediate activation when a person is present in the coverage area for just a brief period of time.
HVAC delay time
Device type = Master
5 s...60 min
[5 min]
Sets the delay before the output is switched OFF whenever movement is no longer detected.
Behaviour at switching on
lock by communication
object
Device type = Master
No reaction
Switch off
Switch on
Value used as output status of the detector when it is triggered (i.e., when movement / presence is
detected) and switched ON.
Behaviour at switching off
lock by communication
object
Device type = Master
No reaction
Switch off
Switch on
Value used as output status of the detector when it is triggered (i.e., when movement / presence is
detected) and switched OFF.