Parameter name
Conditions
Values [Default]
Lighting standby time
Device type = Master
Lux / Time etc. selected by = ETS
Disable
Enable
Enables the standby phase before the output is switched off in absence of detected movement.
If this is disabled, the standby light function is deactivated and the load will turn off directly when
the delay time is expired.
Standby time
Device type = Master
Lux / Time etc. selected by = ETS
Lighting standby time = enabled
30 s...60 min
[5 min]
It is used to set Auto off time, i.e. the duration of the Standby phase
Standby brightness
Device type = Master
Lux / Time etc. selected by = ETS
Lighting standby time = enabled
1...60%
[10%]
It sets the Light brightness level during the Standby phase
Figure 19 - Light control output C1/C2
– Dimming and Standby parameters
14.4 Menus: HVAC control output C3 / C4
The following parameters are repeated for each of the two HVAC Control channels C3 and C4
.
Although not specified below, these options are only listed if the corresponding channels are active.