.  It  will  also  Illuminate  the  Actual  set  temperature,  Actual  water  supply  temperature, 

thermostat/Indoor temperature control icon

,Day icon

and Time 

10.2.

 

Winter mode

: Press the

 On/Off key to light up the 

winter mode icon. The following will also 

illuminate  -  the  actual  setting  temperature,  the  actual  water  outlet  temperature,  thermostat/indoor 

temperature control icon

, heating icon

, water pump icon

, time

 , day

 . 

10.3.

 

HEATING FLOW TEMPERATURE

: The heating flow temperature is shown on the main panel. The default 

temperature is 65°C, however, this should be set to the design temperature of the heating system. The 

boiler can be set between 30°C - 80°C. In most cases 65°C will be correct, however underfloor heating 

systems and low temperature radiator systems maybe as low as 35°C. If using a hot water cylinder most 

systems  would  be  remaining  set  at  65°C.  This  should  be  set  correctly,  or  the  boiler  may  experience 

overheating problems. To set this parameter press the Menu button again which will display ‘Heat’ on 

the front panel. Using the up and down arrow buttons set the desired temperature. 

10.3.1.

 

Press the 

 On/Off key to light up the 

winter mode icon. This will also illuminate the actual 

setting temperature,

 the

 

actual water outlet temperature, the thermostat/ indoor temperature control icon

, heating icon

, water pump icon

, Time

 , heating icon, for the start-

on heating state.

 

10.3.2.

 

Set Temp: Press the “UP/DOWN” Key to adjust the temperature. Then, press the “CONFRIM” Key to 

take effect. 

10.4.

 

FLOW DIFFERENTIAL

: The flow differential temperature is shown on the front panel of the boiler as “CH”. 

This is the difference between the flow and return temperature. When ‘CH’ is set to 15°C and ‘Heat’ is set 

to 65°C the heat exchanger will switch off when the flow temperature reaches 65°C and allow flow to 

continue until the flow temperature reaches 50°C (15°C below 65°C), at which point the heat exchange 

will kick back in. The default setting for this parameter is 15°C.  

10.4.1.

 

Press and Hold 

  Mode until the Display show the “CH” return temperature menu.  

10.4.2.

 

Press “UP/DOWN” to adjust the return temperature setting.  

10.4.3.

 

Press 

 “CONFIRM” to set. (Note: Setting is from 5 ~30 °C, Factory default is 15°C) 

10.5.

 

Radiator 

 mode/ Floor heating 

mode setting: 

 

10.5.1.

 

Press the

 “MODE” key twice in the standby state to enter the radiator / floor heating mode 

selection, 

 

10.5.2.

 

press the “UP / DOWN” to select 

 

10.5.3.

 

Press the

 “CONFIRM” to set.

 

10.6.

 

Time Setting:  

10.6.1.

 

In standby/Summer mode Press 

 “MODE” key 3 times to get hours flashing 

Summary of Contents for ALC1-1PCO12

Page 1: ...EHS Combination and System Boilers Installation Manual Heating for the Renewable Future Please read through the whole instructions before removing the boiler from its packaging and installing and ope...

Page 2: ...ICE UNDER NO CIRCUMSTANCES MUST THIS BOILER BE CONNECTED TO THE MAINS POWER WHILST THE BOILER IS DRY THE BOILER MUST BE FILLED WITH WATER AND PRESSURE TESTED PRIOR TO ELECTRICAL CONNECTION FAILURE TO...

Page 3: ...7 4 1 Flushing 7 4 2 Heating System Fill 7 4 3 Hot Water System Fill 7 5 Electrical Connections 7 5 1 Electricity Connection Precautions 7 5 2 Electrical Supply Connections 7 5 3 Thermostat connectio...

Page 4: ...he boiler at www ehs heating com within the time specified in the warranty terms and conditions This can be found at the back of this manual and on the EHS website The warranty relates to any manufact...

Page 5: ...reaker is used VOLTAGE AND LOAD TEST DONE CABLE SIZE mm BREAKER AMPS 3 6 Check the central heating design is suitable for the application Detailed recommendations are provided in BS EN 12828 and BS EN...

Page 6: ...trical installations IEE Wiring Regulations Seventeenth edition 4 1 7 BS EN 7593 Code of practice for treatment of water in heating systems 5 Unpacking and installation 5 1 These appliances can weigh...

Page 7: ...able Connector 1 4 Single valve 1 14 Water tank pipe 1 24 Body parts 1 5 Pressure switch 1 15 Pressure relief pipe 1 25 Expansion tank 5 litres left side 1 6 Pressure gauge 1 16 Pressure relief valve...

Page 8: ...ponents 1 5 DHW thermostat 60A 17 Water temperature probe D12 1 29 Wire 1 6 Pressure switch 1 18 Water temperature probe D18 1 30 Cable Connector 1 7 Pressure gauge 1 19 Water tank pipe 1 31 Body part...

Page 9: ...the electrical supply then you must install it in a fashion that prevents access to the boiler such as a lockable cupboard The wall that you choose to mount this boiler on should be strong enough to...

Page 10: ...10 www ehs heating com Screw 3 x screws into 3 upper expansion screw bolts Step Four Hang the boiler on the 3 fixed screws Then drill 2 screws into 2 under expansion screws...

Page 11: ...11 www ehs heating com 7 2 Design and connect the plumbing system 7 2 1 Typical S plan Layout for a system boiler...

Page 12: ...12 www ehs heating com 7 2 2 Typical Layout for Combination Boiler...

Page 13: ...d on the flow and return pipework from the boiler Standard ball valves will restrict flow and impede the flow in and out of the boiler which will result in poor performance AUTOMATIC AIRVENTS The EHS...

Page 14: ...red as overtightening of connections can twist and damage the internal pipework of the boiler which is not covered under the warranty An external magnetic filter must be used on all installations 7 3...

Page 15: ...automatic air vent behind the pump in the boiler to ensure its not screwed down It needs to be free moving 7 4 2 3 Connect the filling loop to the water replenishing connection 7 4 2 4 Open the replen...

Page 16: ...carried out when installing high power boilers 7 5 1 2 All electrical connections must be made by a fully qualified electrician 7 5 1 3 All wiring must be carried out in accordance with current IEE BS...

Page 17: ...ernal thermostat and programmer should be used to control the boiler to schedule the hot water or heating These can be fitted as a single programable thermostat or as an individual programmer and ther...

Page 18: ...owing 7 6 1 1 All STEPS in the manual so far have been completed as instructed The boiler must have been filled with water and isolating valves must be in the open position 7 6 1 2 The boiler casing i...

Page 19: ...e Daily 24hr Timing Menu Key 6 Confirm and exit Fault clear key Actual temperature Heating actual outlet temperature bathroom actual outlet temperature Water pump operation status Lit the pump is runn...

Page 20: ...om setting temperature Fault code In winter mode Shows the heating setting temperature In summer mode Shows the Hot water setting temperature Shows Fault Code when a fault occurs Indoor temperature th...

Page 21: ...nd down arrow buttons set the desired temperature 7 6 2 2 1 Press the On Off key to light up the winter mode icon This will also illuminate the actual setting temperature the actual water outlet tempe...

Page 22: ...at the boiler has started to heat the water 7 7 4 Purge Air from The System With the pump running start to purge all air from the system by bleeding all radiators and air vents Once bled the system sh...

Page 23: ...to 5 degrees above current room temperature and check that the boiler heating fires This is confirmed by the Ignition symbol and the Temperature symbol being solidly lit 8 1 2 Let the boiler run for a...

Page 24: ...HEATING PRESSURE SET AT Bar WHAT IS THE INCOMMING MAINS PRESSURE Bar WHAT HAS THE BOILER FLOW TEMPERATURE BEEN SET AT o C WHAT HAS THE BOILER DIFFERENTIAL TEMP BEEN SET AT o C WHAT PUMP SPEED HAS BEE...

Page 25: ...S THE DRAW OF THE APPLIANCE FOR HOT WATER AMPS WHAT SIZE CABLE WAS INSTALLED TO THE APPLIANCE MM2 WHAT IS THE APPROXIMATE CABLE RUN TO THE BOILER M WHAT TYPE OF CABLE HAS BEEN USED Notes BY SIGNING YO...

Page 26: ...ult Heating water temperature is too low 1 If the heating pipework is frozen the boiler will not be able to work 2 Clean pipeline refill the water then switch on EC Display Disconnected from PCB Displ...

Page 27: ...eck whether the heater has leakage and change it 3 Check whether there is leakage situation in the external input power wires and repair the line Dry burning temperature controller trip Display screen...

Page 28: ...inter mode icon This will also illuminate the actual setting temperature the actual water outlet temperature the thermostat indoor temperature control icon heating icon water pump icon Time heating ic...

Page 29: ...timing segment light off And then press MODE and the flashes Press UP DOWN to set the temperature Long press Clock for 3 seconds until the icon is light and timing function starts 10 8 3 1 24 Time on...

Page 30: ...30 www ehs heating com EHS System Boiler 1 Phase...

Page 31: ...31 www ehs heating com EHS Combination Boiler 1 Phase Circuit Diagram Technical Data...

Page 32: ...630mm 380mm 230mm 12 BOILER MAINTENANCE EHS electric boilers do not require maintenance other than the following The heating system must be filled and maintained when the water is cold between a press...

Page 33: ...the last service without invalidating the Warranty 24 If the service is not carried out in accordance with the guidelines within the product installation manual the Warranty cover will become void 25...

Page 34: ...d chemical treatments inhibitor etc Any repair that is needed because of anything other than a fault to the Boiler or failure of the Boiler itself Any 3rd party damage whether accidental negligent mal...