GCU -DG3 User's Guide
EGCON Co,. Ltd
22 Page
16.12. Relay Output Set
NO.
Menu
Setting Scope
Default
1.
RO1
Output setting of indication relay for actual state
63QX
2.
RO2
Output setting of indication relay for actual state
26WX
3.
RO3
Output setting of indication relay for actual state
12X
4.
RO4
Output setting of indication relay for actual state
48X
5.
RO5
Output setting of indication relay for actual state
59X
6.
RO6
Output setting of indication relay for actual state
27GX
7.
RO7
Output setting of indication relay for actual state
51X
8.
RO8
Output setting of indication relay for actual state
51GX
-
Setting lists and explanations
NO.
Indication
Explanation
Other
63QX
Operation in fault of low oil
26WX
Operation in fault of over temperature
12X
Operation in fault of overspeed
48X
Operation in fault of automatic mode start
59X
Operation in fault of overvoltage
27GX
Operation in fault of low voltage
`
51X
Operation in fault of over current
51GX
Operation in fault of over current
88X
Operation in starting output
5X
Operation in pausing output
5EX
Operation in fault of emergency pause
51CX
Operation in blocking input
51TX
Operation in blocking input
23X
Operation in preheating output
AFX
Operation in preliminary fault input
27C
Operation in normal commercial electricity
84G
Operation in normal generating power supply
86X
Operation in fault output of generator
14X
Operation in above IDLE SPEED of generator
13X
Operation in above SYNCHRO SPEED of generator
L-M
Operation when movement is manual mode.
L-A
Operation when movement is automatic mode.
R-M
Operation when remote control is manual mode.
R-A
Operation when remote control is automatic mode.
OFF
Operation when movement mode is OFF.