GCU -DG3 User's Guide
EGCON Co,. Ltd
10 Page
8.2. Please set option setting of GCU-DG3 fitting to generator.
Warning
If setting option differently from generator, there will arise a problem and
especially human accident may arise when detection of overspeed becomes
unoperated on account of wrong setting of [5.PICK-UP SETTING]. Please be
sure to inquire of engine generator manufacturing company the number of ring
gear.
※Alarm machine make sound when input and output sockets of GCU are different from drawing and there
will be indication of 'fault' on LCD when there are wrong parts.
▶
Option setting menu
[2. GEN-SET SETTING] --> [ 1. ENGINE TYPE ] :
Engine fuel control type
- ETS/ETR
[ 2. OPS MODE ] : VAL, CONT, NONUSE
[ 3. WTS MODE ] : VAL, CONT, NONUSE
[ 4. CT RATIO ] :
CT setting
[ 8. COM POWER ] :
How to detect power outage signal
- USED :
Direct input of commercial electricity
-
Input of outer signal(CNT socket)
[4. SPEED SENSOR SET] --> [1.SENSOR ] :
Setting of generator speed sensor
- VOLT :
Sensor of generator speed in generator voltage
- MPU :
Sensor of generator speed in Magnet Pick Up
sensor
[5. PICK-UP SETTING] --> [ 1. GEAR NUMBER ] :
Setting of the number of engine ring gear