16.4. SPEED SENSOR SET
NO.
Menu
Explanation
Default
1
SENSOR
VOLT : Speed sensor in generator
voltage
MPU : Speed sensor in Magnet
PickUp
VOLT
2
DISPLAY
Indicative unit for rotating speed
(RPM) Presently not used
16.5. PICK-UP SETTING
NO.
Menu
Explanation
Setting Scope
Default
1
GEAR NUMBER
The number of MAGNET PICK-UP
SENSOR per rotating of generator(The
number of ring gear)
0~ 255 EA
121 EA
16.6. PASSWORD SETTING
NO.
Menu
Explanations and Setting Scope
Default
1
Setting_PW
USE : Using password in option setting
NONUSED : Not Using password in option setting
NONUSED
2
PowerON_PW
USE : Using password at the first start-up
(All operations are useless if not knowing password)
NONUSED : All operations are possible without password
NONUSED
3
Password
_ _ _ _ : Changing password with pressing [DOWN]
1111
4
VALUE
DEFAULT
Yes : Initializing all values of option setting
NO : Not initializing all values of option setting
NO
16.7. P-RELAY ERROR TYPE
NO.
Menu
Contents
Explanations and Setting Scope
1
TYPE
Selection of
using relay
functions
INT. VAL - Using relay functions such as INT. VAL - UVR, OVR,
OCR
NONUSE - Not Using relay functions(only for detection of fault)
Default : (INT. VAL)