GCU -DG3 User's Guide
EGCON Co,. Ltd
19 Page
16.3. GEN-PROTECTIVE SET
NO.
Menu
Explanations
Setting Scope
Default Value
1
GEN UVR
Detective setting of low-voltage
70~ 220 Vac
180.0 Vac
2
OPE. UVR
Waiting time for low-voltage
detection
0 ~ 59 sec
5 sec
3
GEN OVR
Setting of over-voltage detection
100~ 300 Vac
235.0 Vac
4
OPE. OVR
Waiting time for over-voltage
detection
0 ~ 59 sec
1 sec
5
GEN OCR
Setting of over-current detection
2.0 ~ 8.0
5 A
6
OPE. OCR
Waiting time for over-current
detection
0 ~ 59 sec
5 sec
7
OVER SPEED
Setting of overspeed
1000~2500 RPM
2150
8
OPE SPEED
Waiting time for overspeed
detection
0 ~ 59 sec
0 sec
9
Wrn OIL_P
Setting of low-oil alarm
1.0 ~ 9.9 bar
3.0 bar
10
Err OIL_P
Setting of low-oil fault
1.0 ~ 9.9 bar
1.5 bar
11
OPE OIL_P
Waiting time for low-oil fault
0 ~ 59 sec
1 sec
12
Wrn WATER
Setting of over-temperature alarm
40 ~ 110 ℃
90 ℃
13
Err WATER
Setting of over-temperature
detection
40 ~ 110 ℃
100 ℃
14
OPE WATER
Waiting time for over-temperature
detection
0 ~ 59 sec
5 sec
15
HIGH BATT
Setting of battery overvoltage
20 ~ 40 Vdc
30 Vdc
16
LOW BATT
Setting of battery low-voltage
08 ~ 25 Vdc
08 Vdc
17
OPE BATT
Waiting time for battery overvoltage
and low-voltage detections
0 ~ 59 sec
5 sec
18
CURR UNBAL
Setting of detective scope of
current unbalance
10 ~ 99 %
30 %
19
OPE C_UNBAL
Waiting time for detection of
current unbalance
0 ~ 59 sec
5 sec
20
VOLT UNBAL
Setting of detective scope of
voltage unbalance
10 ~ 99 %
30 %
21
OPE V_UNBAL
Waiting time for detection of
voltage unbalance
0 ~ 59 sec
5 sec
22
Gen Freq MAX
Setting of over-frequency detection
50 ~70 Hz
70 Hz
23
Gen Freq MIN
Setting of low-frequency detection
45 ~ 60 Hz
45 Hz
24
OPE Freq
Waiting time for over-frequency
and low-frequency detection
0 ~ 59 sec
5 sec