GCU -DG3 User's Guide
EGCON Co,. Ltd
18 Page
NO.
Menu
Explanation
Range
Default
1
SDT
Waiting time for starting
0~60sec
3 sec
2
CDT
Waiting time for pausing
0~60min
5 sec
3
OST
Blocking time of starting output after pressing oil
pressure switch
0~60sec
5 sec
4
OFT
Waiting time for detection of oil pressure
0~60sec
5 sec
5
UDT
Waiting time for detection of low-voltage
0~60sec
5 sec
6
STOP
Output time for ETS-typed pause
0~60sec
5 sec
7
MAX CRK_T
Starting output time
0~60sec
7 sec
8
ACB OPEN_T
Waiting time for ACB blocking in automatic mode
0~60sec
5 sec
9
ACB CLOSE_T
Waiting time for ACB input in automatic mode
0~60sec
5 sec
10
B_LED ON
Unlight time after lighting LCD backlight
0~60min
2 min
11
BZ STOP_T
Blocking time of alarm sound
0~60min
2 min
NO.
Menu
Explanations and setting scopes
Default
1
ENGINE TYPE
ETR : A type that engine operates when power supplies to
oil solenoid.
ETS : A type that engine pauses when power supplies to
oil solenoid.
ETR
2
OPS MODE
(Detection of oil
pressure)
SWITCH : Switch use with fault detecting type
SENSER : Sensor use with fault detecting type
NONUSE : Not using fault detecting type
NONUSE
3
WTS MODE
(Detection of
water
temperature)
SWITCH : Switch use with fault detecting type
SENSER : Sensor use with fault detecting type
NONUSE : Not using fault detecting type
NONUSE
4
CT RATIO
CT ratio setting (5/5A~5000/5A)
50/5A
5
START RPM
RPM setting for starting output (400~800RPM)
600RPM
6
START OIL_P
Setting of oil pressure of starting output (3~6bar)
3.0bar
7
COM UVR
Voltage setting of commercial power outage checking
170V
8
COM POWER
USED : Checking commercial power outage with outage
signal
NONUSE : Using outage signal as input of CNT socket
USED
16. SETPOINT
16.1. TIME SETTING
16.2. GEN-SET SETTING