Operation
Page 61
5.5.2
Manual On
You can switch the device on manually if the battery voltage is below 13.2 V
/ 26.4 V (Lead batteries). After the start phase, the device is then in "charg-
ing mode".
The device operates independently of the configured switch-on voltage,
and charges the battery until the cut-off threshold is reached.
(U
batt
>14.2 V / 28.4 V and I
off
< 4.0 A / 2.0 A)
After reaching the switch-off threshold the EFOY Pro fuel cell will switch
into automatic mode.
Please note: The EFOY Pro fuel cell can only start if it is connected to an
intact battery and a filled fuel cartridge. The EFOY Pro fuel cell does not
switch on if the battery is damaged or has been deeply discharged.
INFO:
If the device fails to start, check that the cover lid is not still attached to the
exhaust hose connector. Remove the cover lid.
1.
Press
on the operating panel, or select
"Operating mode" in the main menu. The op-
erating mode selection appears.
2.
Select the "Manual On" operating mode.
3.
Press
[ok]
to confirm your selection.