76
User Interface Display
Explanation
CH Settings
Outdoor reset boost function increases CH set point by
increment (‘Temp’) if CH demand continues beyond pre-set
time limit (‘Time’).
CH set point will continue to increase until set point reaches
195°F / 91°C
Allowable Temperature Increment: 0..36 °F (0..20 °C)
Default Temperature increment: 0 °F (10 °C)
Allowable Time Delay: 1..120 minutes
Default Time Delay: 20 minutes
Maximum boiler power in CH mode limited by adjusting
‘Maximum Power CH’ setting. Boiler will not exceed this
value while operating in CH Mode.
Allowable Range: 1..100%
Default Setting: 100%
DHW Sett
ings
Two DHW modes are available
•
DHW Mode = 0 ‘No DHW
•
DHW Mode is disabled
•
The DHW thermostat input is ignored and the DHW
pump is not used.
•
DHW Mode = 2 ‘DHW Store with Thermostat’
•
Boiler reacts to DHW demand when DHW thermostat
input closes.
•
Boiler modulates to meet DHW demand similar to CH
Mode except DHW set point is used. DHW set point set
in Settings’ submenu found in 'User Menu’.
•
Simultaneous CH & DHW demands handled using DHW
Priority Timing. See ‘DHW Maximum Priority Time’
setting below.
Note:
•
Outdoor reset function disabled while operating in DHW
Mode.
•
Typical when using a DHW indirect storage tank.
• After DHW demand satisfied, boiler enters post purge
mode and DHW pump continues to run for 15 seconds.
0
APPENDIX A - CONTROL MODULE
Summary of Contents for 075 97gb
Page 44: ...44 13 TROUBLE SHOOTING ...
Page 48: ...48 13 TROUBLE SHOOTING ...
Page 50: ...50 13 TROUBLE SHOOTING ...
Page 61: ...61 14 WIRING DIAGRAM 14 1 Connection Diagram ...
Page 62: ...62 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form ...
Page 78: ...78 NOTES ...
Page 79: ...79 Company Address Phone Company Name Tech Initials Service Performed Date ...