12 - RATINGS AND CAPACITIES
12.1
Ratings and Capacities
•
Constructed and hydrostatically tested for maximum
allowable working pressure of 50 psig (pounds per
square inch gauge) (345 kPa) in accordance with ASME
Boiler and Pressure Vessel Code, Section IV, Rules for
Construction of Heating Boilers.
•
Ratings used for elevations up to 2000 ft (600m) above
sea level.
•
For elevations between 2000 ft (600m) and 4500 ft
(1350m), install high altitude control kit
•
For elevations above 4500 ft (1350m) install high
altitude control kit and :
•
USA - Reduce input rate 4% for each 1000 ft
(300m) beyond 4500 ft.
•
Canada - Boiler derates input 10% for every 2000
feet (610 m) above an elevation of 4500 feet (1.37
km).
SEA LEVEL RATINGS
NATURAL AND PROPANE GASES
Size
Boiler Input Rate
(MBH)
(1)
Heating
Capacity
(MBH)
(1)(2)
Net AHRI
Rating, Water
(MBH)
(1)(3)
AFUE
(2)
Maximum
Minimum
075
75
15
69
60
97
100
100
20
91
79
97
(1)
1000
Btu/hr (British Thermal Units Per Hour)
(2)
Heating Capacity and AFUE (Annual Fuel Utilization Efficiency) are based on DOE (Department of Energy) test
procedures.
(3)
Net AHRI Ratings based on piping and pickup allowance of 1.15. Contact Technical Support before selecting boiler for
installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems,
etc.
Summary of Contents for 075 97gb
Page 44: ...44 13 TROUBLE SHOOTING ...
Page 48: ...48 13 TROUBLE SHOOTING ...
Page 50: ...50 13 TROUBLE SHOOTING ...
Page 61: ...61 14 WIRING DIAGRAM 14 1 Connection Diagram ...
Page 62: ...62 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form ...
Page 78: ...78 NOTES ...
Page 79: ...79 Company Address Phone Company Name Tech Initials Service Performed Date ...