APPENDIX A - CONTROL MODULE
1.4
Sequence of Operation
Operational State
User Interface Display
Explanation
Boiler operates in standby mode
until demand for Central Heat (CH) or
Domestic Hot Water (DHW) is detected.
CH or DHW pump is turned based on
type of heating demand.
(CH call is illustrated)
Control Module compares supply
temperature to set point. Boiler proceeds
to ignition if supply temperature is less
than set point.
Combustion Air Blower speed
modulates to prepurge setting for 15
seconds.
Sparking initiated sequence.
S t a n d b y : N o D e m a n d
Heat
Demand?
DHW CH
Pump on
Supply
Temperature
<Setpoint?
15 Second
Prepurge
Ignition
Sparking
No
Yes
No
Yes
After 2 seconds