89
13 - TROUBLE SHOOTING
E128/
R
Safety error for frequent loss of flame
Check the sensing electrode and the cable, flue
recirculation and CO
2
setting.
E129
Safety error for frequently loss of flame
with max correction during the ignition
Check the sensing electrode and the cable, flue
recirculation, enable the automatic calibration
function before to replace components.
E130/
R
528
Flue NTC sensor tripped (warning or
lockout)
Check the thermostat, the correct circulation of
the water and the pump.
Check the status of the primary exchanger
E131
Flue thermostat sensor tripped (lockout)
Check the sensor and wire harness connection and
continuity, correct circulation of the water and the
pump.
Check the status of the primary exchanger.
E132
Ignition failure (<35 tries)
Boiler will continue ignition attempts. Check gas
supply pressure.
E133/
R
0
Gas supply fault (no ignition)
Check the power supply, sensing electrode, spark
electrode and cable. Check gas supply pressure,
flue circulation, continuity between burner and
ground.
E133/
R
1
No ignition (frozen / obstruction
condensate trap)
Check the correct operation of the condensate trap
E134/
R
Gas valve open without gas
Check the gas pressure, sensing electrode, spark
electrode and cable, replace the pcb if it necessary
E135
Internal error
Verify cables; Replace pcb
E154
Plausibility test (flow/return)
Check the correct circulation of the water and the
pump, check the correct position of the sensors
E160
Fan fault
Check the fan and the cable
E169
Air pressure switch closed
Check obstruction on the flue pipe
E178
Low temperature safety thermostat
Check the sensor and the correct circulation of the
water and the pump
E317/162
Wrong power supply electrical frequency
(Hz)
Check the frequency (Hz) and the power supply
E384/164/
R
Fault flame - flame signal where there
should be none
Check the correct operation of the gas valve,
humidity on the pcb and on the detection electrode
E385/165
Under voltage
Check the power supply (V~)
ERROR-
CODE
INTERNAL
CODE
ERROR
ACTION
R
= REQUIRES RESET
ERROR-
CODE
INTERNAL
CODE
ERROR
ACTION
13.5 Errors In Fault History Only (Does not affect boiler operation).
E62
Anti-wind activation with increase of
the minimum fan speed
Check the position of the terminal of the flue duct.
No other action to do
E66
Obstruction of the flue duct at
minimum power
Check obstruction on the flue duct.
E67
Antiwind activation at maximum power
Check the position of the terminal of the flue duct.
PN 240012363 REV. A [08/31/2018]