31
Vent Material Options
GMHB125 & GMCB150
GMBH160 & GMCB200
1
4" / 2" [100 mm / 50 mm] polypropylene coaxial.
1
5"/3" [125mm/80m] polypropylene coaxial.
2
3" [80mm] polypropylene twin pipe.
Shall be polypropylene on BOTH intake and
exhaust.
2
3" [80mm] polypropylene twin pipe.
Shall be polypropylene on BOTH intake and
exhaust.
3
3" [80mm] flexible polypropylene for chimney
exhaust vent, shall have rigid 3" [80mm]
polypropylene on air intake.
3
3" [80mm] flexible polypropylene for chimney
exhaust vent, shall have rigid 3" [80mm]
polypropylene on air intake.
4
3" [80mm] Twin pipe CPVC.
PVC optional on intake ONLY.
4
3" [80mm] Twin pipe CPVC.
PVC optional on intake ONLY.
* Note: Adapters and fittings used with all vent systems shall be from same manufacturer and compatible with the vent
pipe. See list for approved Manufacturers.
6.8 Approved Polypropylene Manufacturers
Note: Maximum equivalent length may vary between
manufacturers.
6 - COMBUSTION AIR AND VENT PIPING
Combustion Air And Vent Pipe Fittings Must Conform With The Following:
Item
Material
Standards
Vent Pipe and Fittings
CPVC schedule 40
ANSI/ASTM D1784/F441
PP (Polypropylene)Pipe and
Components
UL 1738*
ULC S636-08
Pipe
Cement/Primer
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel
®
,
(Polyphenolsulfone) in venting systems shall be prohibited.
WARNING
Use of cellular core PVC for venting flue gas could
result in death, or serious injury.
!
WARNING
Covering non-metallic vent pipe and fittings with
thermal insulation shall be prohibited.
!
Direct vent terminations are designed to work with any standard wall thickness. Installation guidelines for min/
max wall thickness are as follows: Min = 1" [25mm], Max. = 24" [60cm].
* Natalini - Evaluated and approved for use with this boiler.
PN 240012363 REV. A [08/31/2018]