10. SETTINGS AND START UP
Before starting up the heat pump, it will be necessary to set it in order to work with the heating-cooling
system used and to define the main working parameters.
To
set up the equipment, power the heat pump by the external switch. Don’t forget to turn on the heat pump
and the front panel. It will be necessary to drive the internal power switches (upper terminal block) and
control (lower terminal block). Once powered the heat pump, wait until the initial screen appears on front
panel and follow the next steps.
10.1. SELECTING THE FRONT PANEL LANGUAGE
Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> LANGUAGE and
select the front panel language.
10.2. SELECTING THE HEAT PUMP MODEL
Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> CONFIGURATION -
> HEAT PUMP MODEL and select the model ecoGEO used from the available options.
10.3. SOURCE SYSTEM SELECTION
Access INSTALLER MENU (press [Prg] + [Esc] and enter the installer password PW1) -> CONFIGURATION
-> SOURCE . To connect a geothermal source select ground source. If you have a hybrid source or an air
source, use the manual of ECOFOREST ecoAIR..
10.4. SELECTING THE WORKING SCHEME
Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) -> CONFIGURATION -
> SERVICES -> HEATING COOLING.
1. On OPERATION SCHEME screen select the type of installation that is connected to the heat pump
among the options 1 ZONE / 2 ZONE / BUFFER TANK.
1 ZONE for installations with the heat pump directly connected to the heating-cooling system
supplying one temperature level (1 Zone).
2 ZONES for installations with the heat pump directly connected to the heating-cooling system
supplying two different temperature levels controlled by the heat pump (2 Zones).
BUFFER TANK for installations with heat pump connected to an intermediate buffer tank
between the heat pump and the heating-cooling system.
10.5. SELECTING THE INDOOR CONTROL DEVICES
It is possible to control the heat pump by th-Tune inside ambient terminals or by voltage-free contact signals
from one or more relay outputs thermostats. It is also possible use th-Tune terminals and relay thermostats
for the same zone. Access INSTALLER MENU (press [Prg]+[Esc] and enter the installer password PW1) ->
CONFIGURATION -> SERVICES -> HEATING/COOLING.
CONTROL BY TH-TUNE TERMINALS
1. On the screen TH-TUNE select ON/OFF the control by Th-tune terminals.