- pag.13 -
LB408 Oilflam 50.1÷200.1 AB
ABCD
B
LANDIS LMO 44 CONTROL INFORMATION SYSTEM
In case of burner lockout, it is possible to read which cause originated it. Proceed as follows: with the burner in lockout mode (red
LED switched on) keep pressed the lockout button for more than 3 sec. then release it. The red LED will blink according to the
following error code list:
Error Code
Possible cause
2 blinks
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner,
no fuel - Faulty ignition
3 blinks
Free
4 blinks
Extraneous light on burner start-up
5 blinks
Free
6 blinks
Free
7 blinks
Too many losses of flame during operation (limitation of the number of repetitions)
- Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner
8 blinks
Time supervision oil pre-heater
9 blinks
Free
10 blinks
Wiring error or internal error, output contacts
C
SEULEMENT POUR LES COFFRETS DE SECURITE LANDIS LMO 44
En cas de mise en sécurité du brûleur on pourra lire la cause qui l'a provoqué. Dans ce cas, procéder comme il suit: avec
le brûleur en sécurité (LED rouge allumé) appuyer sur le bouton de réarmement pendant plus de trois secondes et le
relâcher. Le LED rouge commencera à clignoter suivant la liste de codes-erreur ci-dessous:
Code-erreur
Cause possible
2 clignotements
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner,
no fuel - Faulty ignition
3 clignotements
Free
4 clignotements
Extraneous light on burner start-up
5 clignotements
Free
6 clignotements
Free
7 clignotements
Too many losses of flame during operation (limitation of the number of repetitions)
- Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner
8 clignotements
Time supervision oil pre-heater
9 clignotements
Free
10 clignotements
Wiring error or internal error, output contacts
D
SOLO PARA EQUIPOS DE CONTROL LLAMA
LANDIS LMO 44
En caso de bloqueo del quemador, es disponible la indicación del origen del bloqueo. Actuar de la manera siguiente:
con el quemador en seguridad (LED rojo encendido) presionar por más de tres segundos el botón de rearme manual y
aflojarlo. El LED rojo empezará a encenderse de luz intermitente, según la lista siguiente de códigos de error:
Códigos de error Posible causa
2 parpadeos
Ausencia de llama al final del tiempo de seguridad en el encendido “TSA”
-Electroválvula defectuosa -revelación de llama defectuoso -regulación del quemador incorrecta
–electrodos defectuosos
3 parpadeos
No utilizado
4 parpadeos
Luz extraña durante la fase de prevarrido
5 parpadeos
No utilizado
6 parpadeos
No utilizado
7 parpadeos
Falta de llama durante el funcionamiento (superado el límite de nº de repeticiones del ciclo)
–Electroválvula defectuosa –Revelación de llama defectuoso –Regulación del quemador incorrecta
8 parpadeos
Control del tiempo de calentamiento del combustible
9 parpadeos
No utilizado
10 parpadeos
Contacto en la salido defectuoso o estropeado dispositivo interno