ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH

Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of  gas nominal feed pressure
(i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; for L.P.G. nom.
pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw up cover M

ADJUSTMENT OF THE AIR PRESSURE SWITCH

Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum by
turning regulator D to position 1. 
- Start the burner and keep in low flame running, while checking that combustion is cor-
rect. Through a small cardboard, progressively obstruct the air intake until to obtain a CO2 increase of
0,5÷0,8% or else, if a pressure gauge is available, connected to pressure port E, until reaching a
pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase the adjustment value of the air
pressure switch until to have the burner lockout. Remove the obstruction from the air intake,
screw on the cover C and start the burner by pressing the control box rearm button.

Note: The pressure measured at pressure port E must be within the limits of the pressure
switch working range. If not, loose the locking nut of screw F and gradually turn the
same: clockwise to reduce the pressure; counterclockwise to increase. At the end tighten the
locking nut.

2,5

5

10

15

50

25

35

3

0

40

45

20

0,4

0,6

0,9

3,0

1

,5

2,

1

1

,

8

2,4

2,7

1,2

I

L

M

N

A

B

C

D

E

F

G

H

SETTING THE FIRING HEAD

+

-

+

-

4 mm

7 mm

Elettrodo di 

a

ccen

s

ione

Elettrodo di rivel

a

zione

"

"

7 mm

IGNITION END IONIZATION ELECTRODES

Ionization Probe

Ignition Electrode

The ionization current is checked by inserting a
microammeter with an end of scale of 50 µA (d.c.)
in series with the ionization probe. A faulty posi-
tion of the electrode can lead to a reduction in the
ionization current and cause a safety cut-out of the
burner due to a flame detection failure. In this case,
check the position of the electrode, its electric con-
nection and the earthing of the burner. The ioniza-
tion current is normally > 20 µA.

24

min. 6 

µ

A

LANDIS LFL1.622

Microamperometro 

fondo scala 50 

µ

A

IONIZATION CURRENT

Microammeter

50 µA end of scale

Summary of Contents for BLU 15000.1 PR

Page 1: ...420010258900 22 10 2009 BLU 15000 1 PR BLU 18000 1 PR Four Head 4 PROGRESSIVE GAS BURNERS EN RU...

Page 2: ...4000 15000 16000 17000 18000 19000 BLU 15000 1 PR B L U 1 8 0 0 0 1 P R combustion chamber pressure capacity TECHNICAL DATA MODELS BLU 15000 1 BLU 18000 1 Thermal power max kcal h 12 931 000 14 655 00...

Page 3: ...R EN E D G 250 200 N H B C A O OVERALL DIMENSIONS MODELS A B C D D1 E F G H I L M N O Blu15000 1 1518 800 718 365 1890 320 1167 530 950 950 M16 320 Blu18000 1 1518 800 718 365 1890 320 1167 530 950 95...

Page 4: ...4 420010258900 BLU 15000 1 18000 1 PR EN 1000 0 0 0 1 800 317 317 317 25 25 5 2 317 317 317 5 2 N 2 1 6 1 M 800 BOILER FLANGE...

Page 5: ...5 420010258900 BLU 15000 1 18000 1 PR EN 1 2 3 6 4 5 BURNER INSTALLATION 1 Nut 2 Washer 3 Gasket 4 Bolt 5 Boiler 6 Gasket...

Page 6: ...6 420010258900 BLU 15000 1 18000 1 PR EN BOILER INSTALLATION...

Page 7: ...1 11000 0 0 2 0 4 1 2 1 4 12000 kW 13000 1 6 1 8 2 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 14000 15000 16000 17000 FLAME LENGTH GAS BURNERS FOUR VERSION FLAME D...

Page 8: ...At the end of the prepurging time the air servocontrol gets to the Low Flame position so that burner ignition is ensured at min output Simultaneously the ignition transformer receives voltage and afte...

Page 9: ...DIS STAEFA Model LFL1 622 1 333 OPERATING CYCLE Ref Description t1 Duration Waiting time for confirmation t2 of air pressure t3 Preventilation time t4 Safety time t5 Pressurizing time Time for enablin...

Page 10: ...gas flow rate using a suitable wrench turn the butterfly valve until you reach the correct gas flow as established by analyzing the combustion process ADJUSTING THE MAXIMUM CAPACITY OF THE GAS Positi...

Page 11: ...ake screw on the cover C and start the burner by pressing the control box rearm button Note The pressure measured at pressure port E must be within the limits of the pressure switch working range If n...

Page 12: ...I 0 SABK SAMA 3 AUTO 2 LOW 1 UP 0 STOP SAL HLBT HLF 1 Termal lock out lamp 2 Working lamp 3 Selector 0 Loking of devoices for operating at intermediate outputs 1 Operation at max output 2 funzionamen...

Page 13: ...that the control systems are properly connected If all these conditions have been satisfied start the bur ner by pressing the reset button Check the burner cycle IF THE BURNER FAILS TO START check th...

Page 14: ...13000 32 34 36 38 40 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 14000 15000 16000 17000 18000 19000 BLU 15000 1 PR B L U 1 8 0 0 0 1 P R MODELS BLU 15...

Page 15: ...00 BLU 15000 1 18000 1 PR RU E D G 250 200 N H B C A O A B C D D1 E F G H I L M N O Blu15000 1 1518 800 718 365 1890 320 1167 530 950 950 M16 320 Blu18000 1 1518 800 718 365 1890 320 1167 530 950 950...

Page 16: ...16 420010258900 BLU 15000 1 18000 1 PR RU 1000 0 0 0 1 800 317 317 317 25 25 5 2 317 317 317 5 2 N 2 1 6 1 M 800 BOILER FLANGE...

Page 17: ...17 420010258900 BLU 15000 1 18000 1 PR RU 1 2 3 6 4 5 1 2 A 3 C 4 CD 5 6 DE GD DH...

Page 18: ...18 420010258900 BLU 15000 1 18000 1 PR RU...

Page 19: ...1 11000 0 0 2 0 4 1 2 1 4 12000 kW 13000 1 6 1 8 2 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 14000 15000 16000 17000 FLAME LENGTH GAS BURNERS FOUR VERSION FLAME D...

Page 20: ...R RU C C C C C C C C C E C 30 66 C 3 2 2 30 E 30 100 C C C riore a 75 ppm 400 50 230 50 C 230 50 D D D A U W U UC DXDGD U C D D E D C DD X D D C Z D U D E Z D D D E E U C U D AD DE D D C GD D D D D D...

Page 21: ...15000 1 18000 1 PR RU D D X 0 min 100 t1 t2 t4 t3 t6 t5 t1 t2 t4 t3 LANDIS STAEFA LFL1 622 C VS VL t1 8 t2 66 t3 2 t4 4 t5 10 t6 10 LANDIS STAEFA SQM 50 481A2 I II III IV V VI VII VIII VIII Versione...

Page 22: ...E 0 AUTO 0 bloccaggio degli apparati per il funzionamento in una posizione intermadia funzionamento alla massima potenza funzionamento alla minima potenza AUTO funzionamento automatico Part 2 Part 3 2...

Page 23: ...L A B C D 1 E 1 2 0 5 0 8 E 0 1 10 C 2 5 5 10 15 50 25 3 5 30 40 45 20 0 4 0 6 0 9 3 0 1 5 2 1 1 8 2 4 2 7 1 2 I L M N A B C D E F G H 4 mm 7 mm Elettrodo di accensione Elettrodo di rivelazione 7 mm 5...

Page 24: ...termico 2 lampada di funzionamento gasolio 3 commutatore 0 bloccaggio degli apparati per il funzionamento in una posizione intermedia 1 funzionamento alla massima potenza 2 funzionamento alla minima p...

Page 25: ...25 420010258900 BLU 15000 1 18000 1 PR RU C C CO2 9 5 9 8 O 75 ppm C C C C C C C C C C C C C C C C C 6...

Page 26: ...26 420010258900 BLU 15000 1 18000 1 PR EN RU...

Page 27: ...27 420010258900 BLU 15000 1 18000 1 PR EN RU...

Page 28: ...rt ecoflam burners com societ soggetta alla direzione e al coordinamento della Ariston Thermo S p A via A Merloni 45 60044 Fabriano An CF 01026940427 ECOFLAM BRUCIATORI S p A reserves the right to mak...

Reviews: