BLU 15000.1 - 18000.1 PR

LANDIS & STAEFA SQM 50.481A2 AIR DAMPER MOTOR

Remove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key provided for. Description: 

I

- High flame opening position adjusting cam (Air)

II

- Limit switch for the air damper position at burner’s shut down

III

- Min. flame opening position adjusting cam (Air).

IV

- Low flame opening position adjusting cam (Air)

V

- Not used cam

VI

- Not used cam

VII

- Not used cam

VIII

- Not used cam

Cam VIII 
is never used

The control box starts the burner
fan, to carry out the prepurging
of the combustion chamber, and
cheks the vent air pressure throu-
gh the air pressure switch. At the
end of prepurging, the ignition
transformer cuts-in and generates
a spark between the electrodes.

At the same time the two gas valves open (Vs safety valve and Vl Low flame working valve). The total safety, in case of missed
ignition or casual burner's flame-out, is granted by a ionisation probe which cuts-in and sets the burner shutdown within the
safety time. In case of gas lack or a major pressure drop, the minimum air pressure switch shuts down the burner.

LANDIS & STAEFA, Model LFL1.622-1.333 OPERATING CYCLE

Ref. Description
t1

Duration Waiting time for confirmation

t2

of air pressure

t

3

Preventilation time

t4

Safety time

t5

Pressurizing time
Time for ena

b

ling operation of the 

main gas valve on minimum capacity

t6

Time for ena

b

ling operation of the 

main gas valve on maximum capacity

Duration

8

66”

2”
4”

10”

10”

Rivelazione

di fiamma

Spia di 

b

locco

Valvola gas

Serranda aria

Farfalla gas

Trasformatore

di accensione

Pressostato aria

Motore ventilatore

Pressostato gas

0

min

100%

t1

t2

t4

t

3

t6

t5

Ciclo di funzionamento normale

Ciclo di funzionamento

in mancanza di fiamma all'accensione

t1

t2

t4

t

3

Consenso

min./max. potenza

Gas manostat

Fan motor

Air Switch

Ignition transformer

Gas valve

Min/max capacity 

ena

b

ling device

Air damper

Gas damper

Flame detector

Cut-out pilot lamp

Normal operating cycle

Operating cycle in the event of 

ignition failureNormal operating cycle

COMBUSTION ADJUSTMENT 

WARNING: In order to have a correct combustion and thermal output adjustments, these must be carried out together
with a combustion analysis, to be executed through suitable devices, taking care that the values are the correct ones and
are in accordance with the local safety regulations. The adjustments must be carried out by qualified and skilled techni-
cians authorised by Ecoflam Bruciatori S.p.A.

EN

Summary of Contents for BLU 15000.1 PR

Page 1: ...420010258900 22 10 2009 BLU 15000 1 PR BLU 18000 1 PR Four Head 4 PROGRESSIVE GAS BURNERS EN RU...

Page 2: ...4000 15000 16000 17000 18000 19000 BLU 15000 1 PR B L U 1 8 0 0 0 1 P R combustion chamber pressure capacity TECHNICAL DATA MODELS BLU 15000 1 BLU 18000 1 Thermal power max kcal h 12 931 000 14 655 00...

Page 3: ...R EN E D G 250 200 N H B C A O OVERALL DIMENSIONS MODELS A B C D D1 E F G H I L M N O Blu15000 1 1518 800 718 365 1890 320 1167 530 950 950 M16 320 Blu18000 1 1518 800 718 365 1890 320 1167 530 950 95...

Page 4: ...4 420010258900 BLU 15000 1 18000 1 PR EN 1000 0 0 0 1 800 317 317 317 25 25 5 2 317 317 317 5 2 N 2 1 6 1 M 800 BOILER FLANGE...

Page 5: ...5 420010258900 BLU 15000 1 18000 1 PR EN 1 2 3 6 4 5 BURNER INSTALLATION 1 Nut 2 Washer 3 Gasket 4 Bolt 5 Boiler 6 Gasket...

Page 6: ...6 420010258900 BLU 15000 1 18000 1 PR EN BOILER INSTALLATION...

Page 7: ...1 11000 0 0 2 0 4 1 2 1 4 12000 kW 13000 1 6 1 8 2 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 14000 15000 16000 17000 FLAME LENGTH GAS BURNERS FOUR VERSION FLAME D...

Page 8: ...At the end of the prepurging time the air servocontrol gets to the Low Flame position so that burner ignition is ensured at min output Simultaneously the ignition transformer receives voltage and afte...

Page 9: ...DIS STAEFA Model LFL1 622 1 333 OPERATING CYCLE Ref Description t1 Duration Waiting time for confirmation t2 of air pressure t3 Preventilation time t4 Safety time t5 Pressurizing time Time for enablin...

Page 10: ...gas flow rate using a suitable wrench turn the butterfly valve until you reach the correct gas flow as established by analyzing the combustion process ADJUSTING THE MAXIMUM CAPACITY OF THE GAS Positi...

Page 11: ...ake screw on the cover C and start the burner by pressing the control box rearm button Note The pressure measured at pressure port E must be within the limits of the pressure switch working range If n...

Page 12: ...I 0 SABK SAMA 3 AUTO 2 LOW 1 UP 0 STOP SAL HLBT HLF 1 Termal lock out lamp 2 Working lamp 3 Selector 0 Loking of devoices for operating at intermediate outputs 1 Operation at max output 2 funzionamen...

Page 13: ...that the control systems are properly connected If all these conditions have been satisfied start the bur ner by pressing the reset button Check the burner cycle IF THE BURNER FAILS TO START check th...

Page 14: ...13000 32 34 36 38 40 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 14000 15000 16000 17000 18000 19000 BLU 15000 1 PR B L U 1 8 0 0 0 1 P R MODELS BLU 15...

Page 15: ...00 BLU 15000 1 18000 1 PR RU E D G 250 200 N H B C A O A B C D D1 E F G H I L M N O Blu15000 1 1518 800 718 365 1890 320 1167 530 950 950 M16 320 Blu18000 1 1518 800 718 365 1890 320 1167 530 950 950...

Page 16: ...16 420010258900 BLU 15000 1 18000 1 PR RU 1000 0 0 0 1 800 317 317 317 25 25 5 2 317 317 317 5 2 N 2 1 6 1 M 800 BOILER FLANGE...

Page 17: ...17 420010258900 BLU 15000 1 18000 1 PR RU 1 2 3 6 4 5 1 2 A 3 C 4 CD 5 6 DE GD DH...

Page 18: ...18 420010258900 BLU 15000 1 18000 1 PR RU...

Page 19: ...1 11000 0 0 2 0 4 1 2 1 4 12000 kW 13000 1 6 1 8 2 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 14000 15000 16000 17000 FLAME LENGTH GAS BURNERS FOUR VERSION FLAME D...

Page 20: ...R RU C C C C C C C C C E C 30 66 C 3 2 2 30 E 30 100 C C C riore a 75 ppm 400 50 230 50 C 230 50 D D D A U W U UC DXDGD U C D D E D C DD X D D C Z D U D E Z D D D E E U C U D AD DE D D C GD D D D D D...

Page 21: ...15000 1 18000 1 PR RU D D X 0 min 100 t1 t2 t4 t3 t6 t5 t1 t2 t4 t3 LANDIS STAEFA LFL1 622 C VS VL t1 8 t2 66 t3 2 t4 4 t5 10 t6 10 LANDIS STAEFA SQM 50 481A2 I II III IV V VI VII VIII VIII Versione...

Page 22: ...E 0 AUTO 0 bloccaggio degli apparati per il funzionamento in una posizione intermadia funzionamento alla massima potenza funzionamento alla minima potenza AUTO funzionamento automatico Part 2 Part 3 2...

Page 23: ...L A B C D 1 E 1 2 0 5 0 8 E 0 1 10 C 2 5 5 10 15 50 25 3 5 30 40 45 20 0 4 0 6 0 9 3 0 1 5 2 1 1 8 2 4 2 7 1 2 I L M N A B C D E F G H 4 mm 7 mm Elettrodo di accensione Elettrodo di rivelazione 7 mm 5...

Page 24: ...termico 2 lampada di funzionamento gasolio 3 commutatore 0 bloccaggio degli apparati per il funzionamento in una posizione intermedia 1 funzionamento alla massima potenza 2 funzionamento alla minima p...

Page 25: ...25 420010258900 BLU 15000 1 18000 1 PR RU C C CO2 9 5 9 8 O 75 ppm C C C C C C C C C C C C C C C C C 6...

Page 26: ...26 420010258900 BLU 15000 1 18000 1 PR EN RU...

Page 27: ...27 420010258900 BLU 15000 1 18000 1 PR EN RU...

Page 28: ...rt ecoflam burners com societ soggetta alla direzione e al coordinamento della Ariston Thermo S p A via A Merloni 45 60044 Fabriano An CF 01026940427 ECOFLAM BRUCIATORI S p A reserves the right to mak...

Reviews: