Ecoflam BLU 15000.1 PR Manual Download Page 13

1

3

420010258900  

BLU 15000.1 - 18000.1 PR

EN

MAINTENANCE

ANNUAL CHECK

The burner (combustion head, electrodes, etc.) must be checked regularly by an authorized technician,
once or twice a year, depending on how much it is used. Before proceeding withe the maintenance check-
up on the burner, it is advisable to check the general condition of the burner and take the following steps:
Disconnect the burner (remove the plug). 
- Close the gas shut-off cock.  
- Remove the cover from the burner, clean the fan and air intake. 
- Clean the combustion head and check the position of the electrodes. 
- Re-install the parts. 
- Check the seal on the gas connectors. 
- Check the state of the flue. 
- Start the burner.  
- Check the combustion parameters

BEFORE TAKING ANY ACTION, CHECK:

- that there is power in the circit and the burner is connected;  
- that the gas pressure is right and the gas shut-off cock is open; 
- that the control systems are properly connected. If all these conditions have been satisfied, start the bur-
ner by pressing the reset button. Check the burner cycle.

IF THE BURNER FAILS TO START:

check the switch, the thermostats, the motor and the gas pressure.

IF THE BURNER PROCEEDS WITH PREVENTILATION BUT CUTS OUT AT THE END OF THE CYCLE:

check the air pressure and the fan. Check the air pressure switch.

IF THE BURNER PROCEEDS WITH PREVENTILATION BUT DOES NOT LIGHT:

check the installation and position of the electrodes. Check the ignition cable. 
Check the ignition transformer. Check the safety device.

IF THE BURNER LIGHTS BUT CUTS OUT AFTER THE SAFETY INTERVAL: 

check that the phase and neutral wires are connected correctly. 
Check the gas solenoid valve. Check the position and connection of the detector electrode.  
Check the detector electrode.  Check the safety device.

IF THE BURNER LIGHTS BUT CUTS OUT AFTER OPERATING FOR A FEW MINUTES:

check the pressure regulator and gas filter. Check the gas pressure with a pressure gauge. Check the detec-
tor value (at least 6 µA).

Summary of Contents for BLU 15000.1 PR

Page 1: ...420010258900 22 10 2009 BLU 15000 1 PR BLU 18000 1 PR Four Head 4 PROGRESSIVE GAS BURNERS EN RU...

Page 2: ...4000 15000 16000 17000 18000 19000 BLU 15000 1 PR B L U 1 8 0 0 0 1 P R combustion chamber pressure capacity TECHNICAL DATA MODELS BLU 15000 1 BLU 18000 1 Thermal power max kcal h 12 931 000 14 655 00...

Page 3: ...R EN E D G 250 200 N H B C A O OVERALL DIMENSIONS MODELS A B C D D1 E F G H I L M N O Blu15000 1 1518 800 718 365 1890 320 1167 530 950 950 M16 320 Blu18000 1 1518 800 718 365 1890 320 1167 530 950 95...

Page 4: ...4 420010258900 BLU 15000 1 18000 1 PR EN 1000 0 0 0 1 800 317 317 317 25 25 5 2 317 317 317 5 2 N 2 1 6 1 M 800 BOILER FLANGE...

Page 5: ...5 420010258900 BLU 15000 1 18000 1 PR EN 1 2 3 6 4 5 BURNER INSTALLATION 1 Nut 2 Washer 3 Gasket 4 Bolt 5 Boiler 6 Gasket...

Page 6: ...6 420010258900 BLU 15000 1 18000 1 PR EN BOILER INSTALLATION...

Page 7: ...1 11000 0 0 2 0 4 1 2 1 4 12000 kW 13000 1 6 1 8 2 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 14000 15000 16000 17000 FLAME LENGTH GAS BURNERS FOUR VERSION FLAME D...

Page 8: ...At the end of the prepurging time the air servocontrol gets to the Low Flame position so that burner ignition is ensured at min output Simultaneously the ignition transformer receives voltage and afte...

Page 9: ...DIS STAEFA Model LFL1 622 1 333 OPERATING CYCLE Ref Description t1 Duration Waiting time for confirmation t2 of air pressure t3 Preventilation time t4 Safety time t5 Pressurizing time Time for enablin...

Page 10: ...gas flow rate using a suitable wrench turn the butterfly valve until you reach the correct gas flow as established by analyzing the combustion process ADJUSTING THE MAXIMUM CAPACITY OF THE GAS Positi...

Page 11: ...ake screw on the cover C and start the burner by pressing the control box rearm button Note The pressure measured at pressure port E must be within the limits of the pressure switch working range If n...

Page 12: ...I 0 SABK SAMA 3 AUTO 2 LOW 1 UP 0 STOP SAL HLBT HLF 1 Termal lock out lamp 2 Working lamp 3 Selector 0 Loking of devoices for operating at intermediate outputs 1 Operation at max output 2 funzionamen...

Page 13: ...that the control systems are properly connected If all these conditions have been satisfied start the bur ner by pressing the reset button Check the burner cycle IF THE BURNER FAILS TO START check th...

Page 14: ...13000 32 34 36 38 40 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 14000 15000 16000 17000 18000 19000 BLU 15000 1 PR B L U 1 8 0 0 0 1 P R MODELS BLU 15...

Page 15: ...00 BLU 15000 1 18000 1 PR RU E D G 250 200 N H B C A O A B C D D1 E F G H I L M N O Blu15000 1 1518 800 718 365 1890 320 1167 530 950 950 M16 320 Blu18000 1 1518 800 718 365 1890 320 1167 530 950 950...

Page 16: ...16 420010258900 BLU 15000 1 18000 1 PR RU 1000 0 0 0 1 800 317 317 317 25 25 5 2 317 317 317 5 2 N 2 1 6 1 M 800 BOILER FLANGE...

Page 17: ...17 420010258900 BLU 15000 1 18000 1 PR RU 1 2 3 6 4 5 1 2 A 3 C 4 CD 5 6 DE GD DH...

Page 18: ...18 420010258900 BLU 15000 1 18000 1 PR RU...

Page 19: ...1 11000 0 0 2 0 4 1 2 1 4 12000 kW 13000 1 6 1 8 2 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 14000 15000 16000 17000 FLAME LENGTH GAS BURNERS FOUR VERSION FLAME D...

Page 20: ...R RU C C C C C C C C C E C 30 66 C 3 2 2 30 E 30 100 C C C riore a 75 ppm 400 50 230 50 C 230 50 D D D A U W U UC DXDGD U C D D E D C DD X D D C Z D U D E Z D D D E E U C U D AD DE D D C GD D D D D D...

Page 21: ...15000 1 18000 1 PR RU D D X 0 min 100 t1 t2 t4 t3 t6 t5 t1 t2 t4 t3 LANDIS STAEFA LFL1 622 C VS VL t1 8 t2 66 t3 2 t4 4 t5 10 t6 10 LANDIS STAEFA SQM 50 481A2 I II III IV V VI VII VIII VIII Versione...

Page 22: ...E 0 AUTO 0 bloccaggio degli apparati per il funzionamento in una posizione intermadia funzionamento alla massima potenza funzionamento alla minima potenza AUTO funzionamento automatico Part 2 Part 3 2...

Page 23: ...L A B C D 1 E 1 2 0 5 0 8 E 0 1 10 C 2 5 5 10 15 50 25 3 5 30 40 45 20 0 4 0 6 0 9 3 0 1 5 2 1 1 8 2 4 2 7 1 2 I L M N A B C D E F G H 4 mm 7 mm Elettrodo di accensione Elettrodo di rivelazione 7 mm 5...

Page 24: ...termico 2 lampada di funzionamento gasolio 3 commutatore 0 bloccaggio degli apparati per il funzionamento in una posizione intermedia 1 funzionamento alla massima potenza 2 funzionamento alla minima p...

Page 25: ...25 420010258900 BLU 15000 1 18000 1 PR RU C C CO2 9 5 9 8 O 75 ppm C C C C C C C C C C C C C C C C C 6...

Page 26: ...26 420010258900 BLU 15000 1 18000 1 PR EN RU...

Page 27: ...27 420010258900 BLU 15000 1 18000 1 PR EN RU...

Page 28: ...rt ecoflam burners com societ soggetta alla direzione e al coordinamento della Ariston Thermo S p A via A Merloni 45 60044 Fabriano An CF 01026940427 ECOFLAM BRUCIATORI S p A reserves the right to mak...

Reviews: