8

420010258900  

BLU 15000.1 - 18000.1 PR

EN

CONNECTION TO THE GAS PIPELINE 

Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verify that
the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gauge connector,
then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats to the desired
temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end of the test the bur-
ner will be enabled to run the start-up sequence.

BURNER START-UP

Before starting the burner, make sure it is mounted correctly. Then check connections are correct according to the dia-
gram and piping is appropriate to the system. Before connecting the burner to the electricity supply, make sure voltage
corresponds to burner plate data. The connection diagram and start-up cycle are shown separately. For wiring from
control box to burner, see the enclosed connection diagram. Pay particular attention to neutral and phase connections :
never exchange them!. Vent air and impurities of gas pipe. Check gas pressure conforms to the limits stated on the bur-
ner plate when connecting a master gauge to the test port provided on the burner. Blower motor starts and pre-purging
begins. Since pre-purging has to be carried out with the max. air delivery, the burner control circuit turns the air dam-
per to the max. delivery position by the air servocontrol in approximately 30 seconds time. When the servocontrol is
fully open, a signal to the electronic control unit starts the 66 seconds pre-purge cycle. At the end of the prepurging
time, the air servocontrol gets to the Low Flame position so that burner ignition is ensured at min. output.
Simultaneously the ignition transformer receives voltage and after 3 seconds (pre-ignition) opens the pilot gas valve.
Fuel flows to the combustion head and ignites. Two seconds after pilot gas valves have opened, the ignition transformer
is excluded from the circuit. In case of no ignition the burner goes to lock-out within two seconds. After 6 sec. open the
working gas valve, governed by the gas firing butterfly valve.Now the burner is operating at the min. firing rate (about
30% of the max. firing rate). The air servocontrol runs at the Low Flame position and in case the temperature control
has to be set at the max. output it goes to a fully open position of air damper and butterfly valve. During the burner-off
periods the air damper closes up fully.  

ELECTRICAL CONNECTIONS

All burners factory tested at 400 V 50 Hz three-phase for motors and 230 V 50 Hz monophase with neutral for auxi-
liary equipment. If mains supply is 230 V 50 Hz threephase withuot neutral, change position of connectors on burner
as in fig. Protect burner supply line with safety fuses and any other devices required by safety standards obtaining in the
country in question.

ADJUSTING THE COMBUSTION PROCESS

IMPORTANT:

to obtain the right adjustment of the combustion and thermal capacity it is important to analyze the reducts of

combustion with the aid of suitable instruments. The combustion and thermal capacity adjustment is done simultaneously,
together with the  analysis of the products of combustion, making sure that the measured values are suitable and that they comply
with current safety standards. On this matter, please refer to the table and figure below.

THESE OPERATIONS MUST BE DONE BY PROFESSIONALLY-QUALIFIED TECHNICIANS.

Summary of Contents for BLU 15000.1 PR

Page 1: ...420010258900 22 10 2009 BLU 15000 1 PR BLU 18000 1 PR Four Head 4 PROGRESSIVE GAS BURNERS EN RU...

Page 2: ...4000 15000 16000 17000 18000 19000 BLU 15000 1 PR B L U 1 8 0 0 0 1 P R combustion chamber pressure capacity TECHNICAL DATA MODELS BLU 15000 1 BLU 18000 1 Thermal power max kcal h 12 931 000 14 655 00...

Page 3: ...R EN E D G 250 200 N H B C A O OVERALL DIMENSIONS MODELS A B C D D1 E F G H I L M N O Blu15000 1 1518 800 718 365 1890 320 1167 530 950 950 M16 320 Blu18000 1 1518 800 718 365 1890 320 1167 530 950 95...

Page 4: ...4 420010258900 BLU 15000 1 18000 1 PR EN 1000 0 0 0 1 800 317 317 317 25 25 5 2 317 317 317 5 2 N 2 1 6 1 M 800 BOILER FLANGE...

Page 5: ...5 420010258900 BLU 15000 1 18000 1 PR EN 1 2 3 6 4 5 BURNER INSTALLATION 1 Nut 2 Washer 3 Gasket 4 Bolt 5 Boiler 6 Gasket...

Page 6: ...6 420010258900 BLU 15000 1 18000 1 PR EN BOILER INSTALLATION...

Page 7: ...1 11000 0 0 2 0 4 1 2 1 4 12000 kW 13000 1 6 1 8 2 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 14000 15000 16000 17000 FLAME LENGTH GAS BURNERS FOUR VERSION FLAME D...

Page 8: ...At the end of the prepurging time the air servocontrol gets to the Low Flame position so that burner ignition is ensured at min output Simultaneously the ignition transformer receives voltage and afte...

Page 9: ...DIS STAEFA Model LFL1 622 1 333 OPERATING CYCLE Ref Description t1 Duration Waiting time for confirmation t2 of air pressure t3 Preventilation time t4 Safety time t5 Pressurizing time Time for enablin...

Page 10: ...gas flow rate using a suitable wrench turn the butterfly valve until you reach the correct gas flow as established by analyzing the combustion process ADJUSTING THE MAXIMUM CAPACITY OF THE GAS Positi...

Page 11: ...ake screw on the cover C and start the burner by pressing the control box rearm button Note The pressure measured at pressure port E must be within the limits of the pressure switch working range If n...

Page 12: ...I 0 SABK SAMA 3 AUTO 2 LOW 1 UP 0 STOP SAL HLBT HLF 1 Termal lock out lamp 2 Working lamp 3 Selector 0 Loking of devoices for operating at intermediate outputs 1 Operation at max output 2 funzionamen...

Page 13: ...that the control systems are properly connected If all these conditions have been satisfied start the bur ner by pressing the reset button Check the burner cycle IF THE BURNER FAILS TO START check th...

Page 14: ...13000 32 34 36 38 40 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 14000 15000 16000 17000 18000 19000 BLU 15000 1 PR B L U 1 8 0 0 0 1 P R MODELS BLU 15...

Page 15: ...00 BLU 15000 1 18000 1 PR RU E D G 250 200 N H B C A O A B C D D1 E F G H I L M N O Blu15000 1 1518 800 718 365 1890 320 1167 530 950 950 M16 320 Blu18000 1 1518 800 718 365 1890 320 1167 530 950 950...

Page 16: ...16 420010258900 BLU 15000 1 18000 1 PR RU 1000 0 0 0 1 800 317 317 317 25 25 5 2 317 317 317 5 2 N 2 1 6 1 M 800 BOILER FLANGE...

Page 17: ...17 420010258900 BLU 15000 1 18000 1 PR RU 1 2 3 6 4 5 1 2 A 3 C 4 CD 5 6 DE GD DH...

Page 18: ...18 420010258900 BLU 15000 1 18000 1 PR RU...

Page 19: ...1 11000 0 0 2 0 4 1 2 1 4 12000 kW 13000 1 6 1 8 2 kcal h x 1000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 14000 15000 16000 17000 FLAME LENGTH GAS BURNERS FOUR VERSION FLAME D...

Page 20: ...R RU C C C C C C C C C E C 30 66 C 3 2 2 30 E 30 100 C C C riore a 75 ppm 400 50 230 50 C 230 50 D D D A U W U UC DXDGD U C D D E D C DD X D D C Z D U D E Z D D D E E U C U D AD DE D D C GD D D D D D...

Page 21: ...15000 1 18000 1 PR RU D D X 0 min 100 t1 t2 t4 t3 t6 t5 t1 t2 t4 t3 LANDIS STAEFA LFL1 622 C VS VL t1 8 t2 66 t3 2 t4 4 t5 10 t6 10 LANDIS STAEFA SQM 50 481A2 I II III IV V VI VII VIII VIII Versione...

Page 22: ...E 0 AUTO 0 bloccaggio degli apparati per il funzionamento in una posizione intermadia funzionamento alla massima potenza funzionamento alla minima potenza AUTO funzionamento automatico Part 2 Part 3 2...

Page 23: ...L A B C D 1 E 1 2 0 5 0 8 E 0 1 10 C 2 5 5 10 15 50 25 3 5 30 40 45 20 0 4 0 6 0 9 3 0 1 5 2 1 1 8 2 4 2 7 1 2 I L M N A B C D E F G H 4 mm 7 mm Elettrodo di accensione Elettrodo di rivelazione 7 mm 5...

Page 24: ...termico 2 lampada di funzionamento gasolio 3 commutatore 0 bloccaggio degli apparati per il funzionamento in una posizione intermedia 1 funzionamento alla massima potenza 2 funzionamento alla minima p...

Page 25: ...25 420010258900 BLU 15000 1 18000 1 PR RU C C CO2 9 5 9 8 O 75 ppm C C C C C C C C C C C C C C C C C 6...

Page 26: ...26 420010258900 BLU 15000 1 18000 1 PR EN RU...

Page 27: ...27 420010258900 BLU 15000 1 18000 1 PR EN RU...

Page 28: ...rt ecoflam burners com societ soggetta alla direzione e al coordinamento della Ariston Thermo S p A via A Merloni 45 60044 Fabriano An CF 01026940427 ECOFLAM BRUCIATORI S p A reserves the right to mak...

Reviews: