BURNER SETTINGS
BOILER MODEL
15/21
MAXIMUM OUTPUT
Btu/hr
72000
Kw/hr
21
FACTORY SETTING
Btu/hr
63000
Kw/hr
18.5
NOZZLE SIZE
0.55 80 deg H
OIL PRESSURE
Bar
8
BURNER AIR
SETTING
7
SMOKE
0
CO
2
%
11.5
FLUE GAS
TEMPERATURE
°C
80
WATER
INLET/RETURN
mm
22
WATER
OUTLET/FLOW
mm
22
CONDENSATE FLOW
mm
22 pvc rigid pipe
2MAX OPERATING
PRESS
Bar
2.5
BOILER EFFICIENCY*
SEDBUK A RATING
%
98
%
93.5
Electrical Power
230/240 V 50 Hz
Fuse
5 amp
SERVICE REQUIREMENTS
The boilers are serviced through an access panel at the front. A service access space of at least
700mm should be made available at the front of the boiler.
THE HEARTH
The temperature of the surface below the boiler is less than 85°C. If the floor under the boiler is of
combustible material, then protection such as steel should be fitted between the boiler and the floor.
Consideration should be given to the weight of the filled boiler; the floor must provide adequate
support. Please consult the building regulation for safe floor loadings.
CONTROL PANEL
The boiler control panel is factory fitted prior to despatch. The phials of the Control and High Limit
Thermostat are inserted into the pockets situated on the left hand side of the boiler heat exchanger.