Safety

Important notices which help provide safe burner
operation will be found in this section. To avoid personal
injury and damage to the property or facility, the following
warnings must be observed. All involved personnel should
read this entire manual carefully before attempting to start
or operate this system. If any part of the information in this
manual is not understood, contact Eclipse before
continuing.

Safety Warnings

  The burners, described herein, are designed to mix

fuel with air and burn the resulting mixture. All fuel
burning devices are capable of producing fires and
explosions if improperly applied, installed,
adjusted, controlled or maintained.

 Do 

not 

bypass 

any 

safety 

feature; 

fire 

or 

explosion

could result.

  Never try to light a burner if it shows signs of

damage or malfunction.

  The burner and duct sections are likely to have

HOT surfaces. Always wear the appropriate
protective equipment when approaching the
burner.

  Eclipse products are designed to minimize the use

of materials that contain crystalline silica.
Examples of these chemicals are: respirable
crystalline silica from bricks, cement or other
masonry products and respirable refractory
ceramic fibers from insulating blankets, boards, or
gaskets. Despite these efforts, dust created by
sanding, sawing, grinding, cutting and other
construction activities could release crystalline
silica. Crystalline silica is known to cause cancer,
and health risks from the exposure to these
chemicals vary depending on the frequency and
length of exposure to these chemicals. To reduce
the risk, limit exposure to these chemicals, work in
a well-ventilated area and wear approved personal
protective safety equipment for these chemicals.

  This manual provides information regarding the

use of these burners for their specific design
purpose. Do not deviate from any instructions or
application limits described herein without written
approval from Eclipse.

Capabilities

Only qualified personnel, with sufficient mechanical
aptitude and experience with combustion equipment,
should adjust, maintain or troubleshoot any mechanical or
electrical part of this system. Contact Eclipse for any
needed commissioning assistance.

Operator Training

The best safety precaution is an alert and trained
operator. Train new operators thoroughly and have them
demonstrate an adequate understanding of the
equipment and its operation. A regular retraining schedule
should be administered to ensure operators maintain a
high degree of proficiency. Contact Eclipse for any needed
site-specific training.

Replacement Parts

Order replacement parts from Eclipse only. All Eclipse
approved valves or switches should carry UL, FM, CSA,
CGA and/or CE approval where applicable.

DANGER

WARNING

NOTICE

2

Summary of Contents for RatioMatic RM Series

Page 1: ...Eclipse RatioMatic Burners RM Series Version 5 12 3 2014 Installation Guide 110...

Page 2: ...and Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection...

Page 3: ...efractory Block Curing Schedule 9 Gas Piping 9 Setting Ignitor Location RM1000 RM3000 11 Checklist After Installation 11 Adjustment Start Stop 12 Adjustment Procedure 12 Step 1 Reset the System 12 Ste...

Page 4: ...been written for people who are already familiar with all aspects of a nozzle mix burner and its add on components also referred to as the burner system These aspects are Installation Use Maintenance...

Page 5: ...by sanding sawing grinding cutting and other construction activities could release crystalline silica Crystalline silica is known to cause cancer and health risks from the exposure to these chemicals...

Page 6: ...rom UL FM CSA European EN 746 2 with CE mark from TuV Gastec Advantica Electrical Wiring All the electrical wiring must comply with all applicable local codes and or standards such as NFPA Standard 70...

Page 7: ...and explosions There are two different types of flame sensors UV scanner and flamerod UV Scanner The UV Scanner must be compatible to the flame monitoring control that is used Refer to the manual of...

Page 8: ...n around the combustor to a depth not beyond the nozzle position as illustrated Figure 3 4 Alloy Combustor Placing insulation around the combustor beyond the burner nozzle position will decrease combu...

Page 9: ...n The recommended curing schedule is Ambient to 600 F 315 C at 100 F 55 C per hour 600 F 315 C to 1000 F 540 C at 25 F 14 C per hour Hold the refractory block at 1000 F 540 C for 12 hours Cool or rais...

Page 10: ...fice optional and at least 4 96mm long after downstream from the start gas orifice Figure 3 8 Bypass Start Gas Piping Please verify that piping complies with all applicable codes and or standards Pilo...

Page 11: ...e monitoring and control system are properly installed This includes verifying that all the switches are installed in the correct locations all wiring pressure and impulse lines are properly connected...

Page 12: ...s a flame failure 5 Activate the pressure switches and other limit interlocks Be sure the switches fail as intended in the event of a power failure If simulated limits or simulated flame failure do no...

Page 13: ...fly valve See Figure 4 5 c Rotate the air butterfly valve shaft to a fully closed position Holes in the butterfly valve will supply low fire air When firing into a positive chamber pressure rotate the...

Page 14: ...ocedure Figure 4 6 BV shaft shown in closed position WARNING Main gas shut off valve train NC NC Main gas shut off valve train NC NC Low fire start without high turndown option Procedure A Main gas sh...

Page 15: ...flow with bias adjusting screw for lowest gas flow that maintains a stable flame signal clockwise for more fuel counterclockwise for less fuel 9 Verify low fire flame a Shut off gas When chamber tempe...

Page 16: ...amber temperature is below 250 F 121 C shut off combustion air blower b Restart combustion air blower and ignite burner c Verify repeatability of ignition and low fire flame signal Procedure C Bypass...

Page 17: ...ent NOTE When firing into negative or fluctuating chamber pressures a higher bypass gas flow may be necessary 10 Verify the bypass gas flame a Shut off gas When chamber temperature is below 250 F 121...

Page 18: ...ame monitoring relay literature for a description of an erratic flame signal 8 If burner has gone out repeat ignition sequence Turn internal bypass adjusting screw a half turn counterclockwise to incr...

Page 19: ...n 3 Measure the gas differential pressure as shown in Figure 4 19 4 If necessary adjust the gas flow with the butterfly valve The flame should be clear blue If the flame is yellow see Troubleshooting...

Page 20: ...l while at the same time noting if related equipment closes or stops as specified by the manufacturer Test the flame safeguard by manually shutting off the gas to the burner 8 Test the manual gas shut...

Page 21: ...e pilot adjusting valve or bypass valve is not open far enough Adjust bypass or low fire gas Not enough gas Start gas solenoid valve does not open Check the solenoid valve coil for proper operation Re...

Page 22: ...pressure going into the ratio regulator is too low Adjust the gas pressure Cannot initiate a start sequence Air pressure switch has not made contact Check air pressure switch adjustment Check air fil...

Page 23: ...ply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 001 From To Multiply By actual cubic foot h acfh actual cubic meter h am h...

Reviews: