Installation instructions

 

Features 

- Silent running centrifugal pump with 1,5m power cord

- Full ball bearings in drive shaft

- Pump unit encapsulated in a IP55-rated case (EE400M only)

- Check valve to prevent back-flow of liquid into the unit

- Overflow safety alarm switch (EE400M and EE300 only) 

- Ultra-compact size

Application 

The Eckerle condensate pumps EE400M, EE300 and EE150 are 

designed to automatically remove liquid from air-conditioners, evapo

-

rator coils and/or an oil or gas condensing warm air boilers (EE400M 

and EE300 only). The pumps are made from a tough ABS plastic so will 

resist corrosion, impact and thermal influences. (pH ≥ 3, max. 70C°).

Specifications EE400M 

- Electrical spec.:    

230V, 50/60Hz, 65VA 

- Protection class:   

IP55

- Alarm switch:  

 

max. 230V, 8A (NO/NC) ohmic load

  (potential free) 

 

NC = red, NO = black, COM = white

- Weight:   

 

approx. 1600 g 

- Tank capacity:  

 

max. 0,5 l 

- Dimensions:  

 

185 x 85 x 100 (L x W x H) 

- Pressure hose dia.:  

8 x 2 mm

- Limit of use:  

 

40l/h (approx. 400KW) @ 2,5m head

  S3 intermittant duty, 6 s on – 20 s off

- Pump unit of EE400M can be used in a separate pan.

  Maximum fill level: 70 mm

Theroretical flow rate l/h

head (m)

approx. 350

0

approx. 280

1

approx. 220

2

approx. 100

3

0

4

Specifications EE300 

- Electrical spec.:    

230V, 50/60Hz, 65VA

- Protection class:   

IP20

- Alarm switch:  

 

max. 230V, 3A (NO/NC) ohmic load

  (potential free) 

 

NC = red, NO = black, COM = white

- Weight:   

 

approx. 1600 g 

- Tank capacity:  

 

max. 1 l 

- Dimensions:  

 

200 x 105 x 160 (L x W x H) 

- Pressure hose dia.:  

8 x 2 mm

- Limit of use:  

 

30l/h (approx. 300KW) @ 2,5m head

  S3 intermittent duty, 6 s on – 20 s off

Theroretical flow rate l/h

head (m)

approx. 200

0

approx. 150

1

approx. 100

2

approx. 50

3

0

4

Specifications EE150 

- Electrical spec: 

 

230V, 50/60Hz, 48VA 

- Protection class:   

IP20

- Weight:   

 

approx. 850 g 

- Tank capacity:  

 

max. 0,2l 

- Dimensions:  

 

165 x 65 x 85 (L x B x H) 

- Pressure hose dia.: 

8 x 2 mm

- Limit of use:  

 

10l/h (approx. 30KW) @ 0,8m head

  S3 intermittant duty, 1 s on – 5 s off

 

Theroretical flow rate l/h

head (m)

approx. 120

0

approx.80

1

0

1,5

Installation 

1. Carefully unpack the unit, check for damage and make sure that all of  

    the required parts are included. The units are thoroughly tested before  

    packing to insure safe delivery and operation. If there is any sign 

    of damage due to shipment, return it to the place of purchase for  

    repair or replacement. 

2. Choose a mounting location near the air-conditioner or boiler. 

    The pump must be mounted level. And the inlet must be below the  

    lowest drain. 

3.The pump should be mounted in a way that the cover (EE400M)  

  

   and/or the pump unit inside (EE150 and EE300) can be removed 

   easily for cleaning purposes. 

Connecting the piping 

1. Run flexible tubing or pipe from the condensate drain on the  

    evaporator pan and/or drain from boiler to the inlet hole on the pump. 

    This drain line should have a continuous downward slope to  

    allow gravity flow. Cut the end of the line at an angle so the end  

    does not close off on the bottom of the pump’s tank. 

2. Connect the discharge line by hand- tighten the cap nut of the  

    check valve in a clockwise direction. Flexible tubing with a size of  

    8x2 mm will be suitable. Extend the discharge line straight up from  

    the pump to the highest point, run the discharge line to a drain with 

    a downward slope. 

Note: Condensates discharged from condensing boilers can con-

tain residual contaminants like soot & unburned hydrocarbons. In 

these systems, it is essential that the contaminated condensates 

are treated before being delivered to the pump. Failure to comply 

with these requirements can cause equipment malfunction.

Wiring

 

Shut off electrical power at the fuse box before making any wiring 

connections. All wiring must be done according to local and/or applicable 

national codes. 

1. Main power connection: All pumps are equipped with a 1.5 m power  

    cord. Connect this cord to a constant line voltage source, not a fan  

    or other device that may run intermittently. 

2. Overflow alarm switch: The pump models EE400M and EE300 are  

    equipped with an overflow alarm switch (NO/NC) which should be   

    connected. The alarm contact of the EE400M will be activated with a  

    5s time delay and only works if the main power line is connected.

- 4 -

GB

Summary of Contents for 22213

Page 1: ...Installationsanweisung Installation instructions Instruction d installation Istruzioni per l installazione Instrucciones bomba de condensados Руководствo по применению EE300 EE150 EE400M ...

Page 2: ... gewährleisten wurden die Pumpen vom Hersteller gründlich getestet bevor sie transportsicher verpackt wurden Falls Mängel auftreten oder gar erkennbar sind senden Sie die Pumpe zur Reparatur bzw Ersatzlieferung an Ihren Lieferanten zurück 2 Wählen Sie einen Montageplatz in der Nähe Ihres Klima oder Brennwertgerätes Die Pumpe muss waagerecht montiert werden 3 Die Zuleitung muss fallend und ohne Que...

Page 3: ...il erhältlich Modell Artikel Nummer Bezeichnung EE150 EE400M 22214 Rückschlagventil EE300 22213 Rückschlagventil Störungssuche Treten Störungen an der Pumpe auf beachten Sie folgende Hinweise 1 Pumpe läuft nicht a Überprüfen Sie die Stromversorgung der Pumpe b Prüfen Sie ob Kondensat abgepumpt wird bzw im Tank vorhanden ist c Überprüfen Sie ob sich die Schwimmer frei bewegen lassen und bei der Auf...

Page 4: ...allation 1 Carefully unpack the unit check for damage and make sure that all of the required parts are included The units are thoroughly tested before packing to insure safe delivery and operation If there is any sign of damage due to shipment return it to the place of purchase for repair or replacement 2 Choose a mounting location near the air conditioner or boiler The pump must be mounted level ...

Page 5: ...shooting If the pump does not function properly refer to the following 1 Unit does not run a Check the power supply b Check the appliance to see if condensation is actually being generated c Check to make sure the pump float mechanism moves freely and clicks the activation switch when moved up and down EE150 EE400M quiet click noise only due to construction type of switch d Check the drain line s ...

Page 6: ...hauteur de refoulement S3 cycle de travail max 6 ON 5 OFF Débit théorique l h Hauteur de refoulement m max 120 0 max 80 1 0 1 5 Installation 1 Veuillez sortir la pompe de son emballage avec précaution Effectuez un contrôle visuel pour détecter d éventuelles détério rations et pour déterminer si tous les accessoires ont été livrés Les pompes sont soumises à des tests approfondis avant d être emball...

Page 7: ...rdre si on serre trop fort Pièces de rechange Comme pièces de rechange pour les deux pompes nous pouvons vous livrer l embout de refoulement avec clapet antiretour intégré type de pompe Numéro de l article Désignation EE150 EE400 22214 Clapet anti retour EE300 22213 Clapet anti retour Dépannage Au cas où la pompe présenterait un disfonctionnement quelconque veuillez observer les remarques suivante...

Page 8: ...a di essere imballate per il trasporto le nostre pompe sono sottoposte a severe prove di funzionamento al fine di garantirne la sicurezza operativa Qualora costatiate eventuali difetti inviateci la pompa per riparazione o sostituzione 2 Per l installazione della pompa scegliete un posto nei pressi del l impianto di condizionamento o della caldaia a condensazione La pompa dovrà essere montata in po...

Page 9: ...no indicate alcune cause di guasti e o anomalie che si pos sono presentare alla pompa ed i relativi rimedi 1 La pompa non funziona a Verificate che ci sia alimentazione elettrica b Controllate l unità verificando la presenza e o il pompaggio della condensa c Verificate che il galleggiante si muova liberamente e che al sollevamento abbassamento si avverta uno scatto e Verificate che il condotto di ...

Page 10: ...Desembalar con mucho cuidado la bomba de condensados comprobar que no tiene ningún defecto y que contiene todos los elementos de la misma 2 Elegir un lugar para instalar la bomba que esté situado cerca del aparato de aire acondicionado La aspiración de la bomba debe situarse por debajo del nivel más bajo de condensados o en todo caso a la misma altura 3 La bomba de condensados debe instalarse de t...

Page 11: ...scarga con la válvula de retención integrada está dispo nible como pieza de recambio Se puede utilizar tanto para la EE150 como para la EE400M modelo Número de artículo Designación EE150 EE400 22214 la válvula de retención EE300 22213 la válvula de retención RESOLUCIÓN DE PROBLEMAS Si la bomba no trabaja correctamente proceder de la siguiente forma 1 Si la bomba no funciona a Comprobar la toma de ...

Page 12: ...те блок Проверьте возможные повреждения и убедитесь что все требуемые части имеются в наличии Блок перед упаковкой тщательно тестируется для обеспечения безопасной транспортировки и эксплуатации Если существует какой либо признак повреждения во время транспортировки верните блок в место покупки для ремонта или замены 2 Выберете место установки около воздушного кондиционера или бойлера Помпа должна...

Page 13: ...ющее 1 Блок не включается а Проверьте питание электроэнергией б Проверьте установку и убедитесь что конденсат действительно образуется в Убедитесь что поплавковый механизм помпы свободно движется и при его перемещении вверх и вниз срабатывает выключатель помпы ЕЕ150 и ЕЕ400М издают тихий щелчок связанный с конструкцией выключателя г Проверьте трубки слива в помпу на предмет свободного тока Внимани...

Page 14: ...a przerywana 1 s praca 5 s przerwa Teoretyczna Wydajność tłoczenia l h Wysokość tłoczenia m maks 120 0 maks 80 1 0 1 5 Instalacja 1 Wyjąć pompę ostrożnie z opakowania Sprawdzić czy urządzenie nie posiada ewentualnych uszkodzeń oraz czy wszystkie elementy dodatkowe są w opakowaniu W celu zapewnienia właściwego działania producent testuje pompy przed spakowaniem i transportem W przypad ku stwierdzen...

Page 15: ...e zostać uszkodzony pierścień typu O Części zamienne Do obu pomp króciec opróżniania ze zintegrowanym zaworem zwrot nym model Numer artykułu oznaczenie EE150 EE400 22214 zawór zwrotny EE300 22213 zawór zwrotny Ustalanie uszkodzeń błędnego działania W przypadku występowania błędów w działaniu należy przestrzegać następujących wskazówek 1 Pompa nie działa a Sprawdzić podłączenie do sieci b Sprawdzić...