Firmware V1.41 V1
08.11.2022
74/219
•
•
•
•
•
•
•
•
•
and unloaded sequentially but according to the operating time. If a fan must be loaded, the fan with the
shortest operating time is switched on. If a fan must be unloaded, the fan with the longest operating time is
switched off. Furthermore, base load rotation of the fans is performed in this operating mode. If the tG
controller is in the neutral zone for a configurable time
Cycle time F.
(menu 3-7), after expiry of this time, if
available the fan with the shortest time will be loaded and the fan with the longest time unloaded for this.
2.
Cycle time F.
A time can be entered following which, depending on the previously described operating modes, either fan
switching or base load rotation will be performed.
5.6.12 Kickstart
This function monitors long standstill times of individual fans. In the event of exceeding a configurable standstill
time, this fan will be switched on for a short time. This function is intended to prevent the seizure of individual
fans in cold seasons.
Function scope
Support of all control modes of the condenser controller (step, speed, parallel combined and stages
combined)
The kickstart last for 5 seconds for all control modes
A minimum wait time of 5 minutes between one kickstart and the next is implemented
The kickstart is only performed for fault-free (motor cut-out) and enabled fans (System Configuration menu
3-1)
Control modes with an FC are executed at minimum speed (parameter "
Min. speed
", menu 3-2-2-1) during
the kick-start
For the parallel combined control mode, the FC enable (Vent DigOut 1) is also actuated if this is OFF
Parametrisation
Parameter
Menu
Value range
Default
Unit
Description
Fan Kickstart
3-2-2-1
YES / NO
NO
-
The function is activated with YES
Fan Offtime
3-2-2-1
24..240
24
hours
Standstill time of a fan, after which the
kickstart is performed (only visible if
parameter
Fan Kickstart
is set to YES)
Fan Kicklimit
3-2-2-1
0..20
5
Kelvin
tc-Setpoint / tc-Actual difference, from
which the function will be active. For
example for tc-Setpoint = 20 °C,
Fan
Kicklimit
= 5 K. Function would be active
starting from a tc-Actual greater than 15
°C.
(only visible if parameter
Fan Kickstart
is
set to YES)
Restrictions
The function is inactive for measuring circuit errors of the tc actual value
The function is inactive when "Fan off w/comp" (menu 3-2-2-1) is set to YES and all compressors are
switched off
The function is inactive when Service mode (menu 8) is active
5.7 Medium Pressure Regulation
The controller regulates the medium pressure (MP) of a CO
2
system using a PI controller. The required
correcting variable for the regulation is provided via the analogue output 4 (terminals 63/64, 0..10 volts).