5.5 High-Pressure Regulation
The high-pressure is regulated in the controller using a high-pressure valve. The valve is actuated using an
0...10 V signal via the analogue output 3 (terminals 57/58).
The control variable, high pressure pc, is measured using a continuous pressure transmitter with linear
characteristic at the analogue input 4 (terminals 44/45). The setpoint for the regulation is calculated depending
on the gas cooler outlet temperature.