ECKELMANN VS 3015 CT Operating	 Instruction Download Page 85

 

 

Firmware V1.41 V1

08.11.2022

85/219



5.9.4  Changes to the Control Behaviour during HRC Mode

Some functionality is handled differently in HRC mode. The key points are listed below.

Monitoring

No high pressure fault is reported.
No compressor disable / unload in the event of high-pressure fault (except for exceeding 

HP EMERG.-OFF

).

The HRC mode is shown on the display of the system centre or operator terminal, 

see also 

Anzeige der 

Betriebszustände

.

HRC mode 

active

: HP-Soll 

HRC

 89 b

HRC-Betrieb 

not active

HP-Soll 89 b 

Regulation of the gas cooler outlet temperature

A fixed speed can be specified for the gas cooler (necessary for integrated outdoor compressor in the gas 
cooler). 
The request is performed via the CAN bus (HRC 3010 A required).

5.9.5  HRC mode parametrisation

Description of the parameters that are necessary for the HRC mode. The parameters mainly refer to the high 
pressure and gas cooler regulation in HRC mode.

No.

Parameter

Menu

Entry

Default

Dim.

Description

1

HRC operation

3-2-2-3

YES / NO

NO

-

Enable of the HR mode

2

WRG-Modus

3-2-2-3

CAN BUS / 
Digital Input

Digital 
input

-

Selection menu for how HR mode should be activated. 
Digital input 

or

 via CAN bus.

3

Standz. WRG

3-2-2-3

0...180

10

Min

Standstill time of the HRC mode after the last 
deactivation. Safety function against continuous 
activation and deactivation of the HR mode due to 
cycling request signal at the digital input or on the 
CAN bus.

4

Verz.Stör.WRG

3-2-2-3

0...720, --

360

Min

An alarm is generated in the case of cycling HRC 
request signal within the Standzeit WRG. The 
generation of this alarm can be delayed.

5

Sollw.Schieb.

3-2-2-3

YES / NO

NO

-

The HP setpoint shift is deactivated / activated via the 
analogue input 6 with this parameter.

Attention:

 Double occupancy of the analogue input 

with the to shift. For the HP setpoint shift via CAN bus, 
this parameter must be set to "NO" and the parameter 
"

WRG-Modus

" must be set to CAN-BUS.

6

Off.ext.Sig.

3-2-2-3

0...25

0

%

Offset on the request signal for HP setpoint shift via 
analogue input 6. This parameter is visible if the 
parameter "

Sollw.Schieb.

" is configured to "YES".

7

tG Anheb.WRG

3-2-2-3

YES / NO

NO

-

Parameter to go to a fixed tg-setpoint in HRC mode. 
This value can be configured with the "

tG-Soll WRG

parameter.

8

tG-Soll WRG

3-2-2-3

0...30

0

°C

tg-setpoint that can be moved to in HR mode 
(dependent on the parameter "

tG Anheb.WRG

", also 

the visibility of the parameter)

9

Lü. AUS im WRG

3-2-2-3

YES / NO

NO

-

The fans in HRC operation can be switched off in 
HRC mode. This parameter must be configured to 
"YES" and the parameter "WRG-Modus" must be set 
to "CAN-BUS" for this. If the "Switch off fan" request 
arrives via the CAN bus, these are unloaded in HR 
mode.

Summary of Contents for VS 3015 CT

Page 1: ...Firmware V1 41 V1 08 11 2022 Doku 1 8 Operating instruction VS 3015 CT Pack Controller for transcritical CO2 systems...

Page 2: ...on line in E EDP Eckelmann Electronic Documentation Platform at www eckelmann de elds You reach all relevant documents for this component directly using the QR code https edp eckelmann de edp lds _06...

Page 3: ...ned control 20 5 3 Configuration of the pressure transmitters 21 5 3 1 Low Pressure Transmitter Z2 LP Z2 22 5 4 Low Pressure Regulation 22 5 4 1 Control Algorithm for LP Control 23 5 4 2 Control Algor...

Page 4: ...Control Algorithm tG with Step Controller 62 5 6 5 1 Switching Times for Fan Motors with Step Controller 62 5 6 5 2 Fan Motors Star Delta Switching 64 5 6 5 3 Parametrisation of the Switching Modes 64...

Page 5: ...High Pressure Monitoring 98 5 12 4 1 High Pressure Monitoring Too High 98 5 12 4 2 High Pressure Monitoring Too Low 99 5 12 4 3 Monitoring of the HP Valve 99 5 12 4 4 Monitoring of the HP Control Err...

Page 6: ...of the internal SIOX using jumper J2 121 6 2 6 Factory Setting of Analogue In and Outputs 121 6 2 7 Power Supply 122 6 2 7 1 Status LEDs 122 6 3 Default parameter settings 123 6 4 Start Up of Speed C...

Page 7: ...Control 165 9 2 2 2 CI 3x00 Store Computer AL 300 Operator Terminal Remote Control 165 9 2 3 Deactivating the Input Lock 166 9 2 3 1 CI 4x00 System Centre Log In and Log Out 166 9 2 3 2 CI 3x00 Store...

Page 8: ...s 213 13 Technical Data VS 3015 CT SIOX 216 13 1 Electrical Data VS 3015 CT SIOX 216 13 2 Mechanical Data VS 3015 CT 217 13 3 Mechanical Data SIOX Extension Module 218 14 Part Numbers and Accessories...

Page 9: ...evere injury or death if the specified instructions are not observed WARNING Instructions with this symbol and or the signal word WARNING warn the user of situations that may cause severe injury or de...

Page 10: ...of text formatting Safety instructions or hazard warnings are composed of four elements The symbol with text e g for DANGER a concise description of the hazard and a description of the possible conseq...

Page 11: ...r it is suitable for your application with regard to its limit values The equipment must be installed in an electrically shielded area within the switch cabinet Before connecting the device it must be...

Page 12: ...such persons The applicable regulations e g DIN EN 60204 EN 50178 DGUV Regulation 3 DIN VDE 0100 0113 must be observed The operating personnel must be instructed in how to handle the system machine an...

Page 13: ...isconnect The entire system to be worked on must be disconnected from the power supply at all poles 2 Secure against reconnection Attach information signs to the disconnected operating equipment stati...

Page 14: ...ng Conductive flooring ESD workstations equipped with suitable tools grounded soldering guns antistatic wrist straps etc Conductive ESD bags conductive plastic containers IC tubes or cartons lined wit...

Page 15: ...xtension module 1 8 NT MP compressors 3 LT compressors up to 12 fans via Modbus or 4 fans via relays VS 3015 CT Basic Module and one SIOX Ejector A separate SIOX extension module is required to contro...

Page 16: ...LDS system RS232 E LDS system communication with building management system and firmware update possibility RS485 with integrated 120 ohm resistor for control of the Modbus analogue module with four...

Page 17: ...Firmware V1 41 V1 08 11 2022 17 219 4 VS 3015 CT Functions The functions in the CO2 booster system can be shown schematically as follows...

Page 18: ...ion module is required The number of compressor capacity stages is then reduced to 3 or 6 Fan control step controller for one circuit systems for control via Modbus with max 12 fans 3 6 fans with sepa...

Page 19: ...t out compressors fans Compressor high pressure limiter Cylinder head temperature Low pressure regulation Medium pressure regulation High pressure regulation Compressor switching frequency Superheat d...

Page 20: ...Switch off controller for 5 seconds and then switch on again Put coding switch 2 of the DIP switch S1 back in the original position Switch off controller and switch on again Restore the configuration...

Page 21: ...ler operates with continuous pressure transmitters with linear characteristic curves The pressure inputs can be adjusted for various transmitters with linear characteristic curves Transmitters with bo...

Page 22: ...suction gas temperature of the LT circuit Z2 circuit a pressure transmitter with a measuring range from 1 to 26 bar must be connected to the analogue input 3 terminals 41 42 of the controller The fun...

Page 23: ...ansmitter with continuous current 4 20 mA or voltage 0 10 V output 5 4 1 Control Algorithm for LP Control The cycle time of the controller is one second The control algorithm depends on the type of co...

Page 24: ...tpoint value plus 1 5 times the NZ and greater than the setpoint value plus 0 5 times the NZ no compressor actuation occurs as it is to be expected that the NZ will shortly be reached D No compressor...

Page 25: ...one step controller day operation 1 10 4 K 3 2 1 4 Neutral Zone Neutral zone step controller night operation 1 10 4 K 5 4 2 2 Compressor Switching Times for Compressor Step Regulation On the one hand...

Page 26: ...t stage 5 4 3 Control Algorithm with LP Combined Control The measured low pressure measured using an A D converter is compared with the setpoint Control error Actual value t0_act Setpoint t0_setp Depe...

Page 27: ...imum speed the fixed speed compressor with the longest operating time is unloaded The speed controlled compressor is accelerated to a value which corresponds to the capacity with the additional fixed...

Page 28: ...ined control of capacity controlled fixed speed compressors a single stage speed controlled compressor is combined with one or more capacity controlled fixed speed compressors Using an adjustment of t...

Page 29: ...es in the circuit is equal to three the second and third relay stages terminals 23 24 and terminals 33 34 are assigned to the FC compressor These capacity stages that are assigned to the FC compressor...

Page 30: ...um FC speed output by the controller is set here This must be selected to be greater than or equal to the minimum frequency to be output by the FC The parameter Min speed has no function for this oper...

Page 31: ...es of the compressor stages and on the other hand to optimally introduce the pack output temporal and control action for the required refrigeration capacity Switching of fixed speed compressors is onl...

Page 32: ...for step controllers and combined control was previously designed so that all compressors in the pack have the same output Now a percentage output can be assigned to each of the compressors Backgroun...

Page 33: ...is set to YES The following points must be observed Input of the percentage proportion between 5 100 The total capacity of all compressors must not exceed 100 any input sum of more than 100 is not pos...

Page 34: ...or Calculated proportion of total flow volume Recorded proportion in menu 3 2 1 1 Compressor outputs and their proportions of the total flow volume 1 12 0 m h 16 39 16 4 2 17 8 m h 24 32 24 3 3 17 8 m...

Page 35: ...perature is provided here either by a Pt1000 temperature sensor that is connected directly to the analogue input terminals 5 6 7 8 of the pack controller or provided via the CAN bus from another pack...

Page 36: ...LoadLevel menu 3 2 1 2 is exceeded on at least one of the associated refrigeration points for the pack it can be assumed that it is no longer possible to reliably maintain the temperature at this thes...

Page 37: ...sk ext to Sch is output If the offset is set to zero no message is output The default value for the signal is Prio 2 If the t0 shift via an external 0 10 volts signal is active the t0 setpoint is calc...

Page 38: ...led due to load shedding are taken into account for the base load rotation The number of running compressor stages is not changed during the base load rotation The base load rotation is only active un...

Page 39: ...oad cut out or oil pressure switch for the speed controlled compressor C1 or C2 any base load rotation is only performed once on the still available fixed speed compressors No base load rotation is pe...

Page 40: ...d shedding and is used for reduction of the network load in the case of any failure of the power supply e g operation of the store using an emergency power generator If the emergency power mode is act...

Page 41: ...ve The valve is actuated using an 0 10 V signal via the analogue output 3 terminals 57 58 The control variable high pressure pc is measured using a continuous pressure transmitter with linear characte...

Page 42: ...ulated in the dead band or this retains the last calculated value 0 0 3 0 0 5 bar VC ramp s Ramp speed of the control signal for the HP valve limitation of the i component 0 04 1 00 0 16 V s HP Ramp m...

Page 43: ...rst start up the HP valve can be actuated manually The parameter Man op must be set between 0 and 100 to the desired value of the HP valve for this If has been entered the opening degree is controlled...

Page 44: ...determination of the HP setpoint in the subcritical range The supercooling can be set in menu 3 2 2 2 using the Subcooling parameter The following graph shows the progression of the high pressure setp...

Page 45: ...n of the HP setpoint requires correct measurement of the gas cooler outlet temperature In the event of measurement errors e g EMC interference in the measuring cable etc see also the instructions in c...

Page 46: ...Firmware V1 41 V1 08 11 2022 46 219...

Page 47: ...der MP accumulator The system design in the ejector version makes it possible to significantly reduce the superheating of the refrigerant at the evaporator outlet of the NT evaporators In addition to...

Page 48: ...s 3 2 2 4 Switch Delta Switch Delta for exceeding the limit for switching the ejector stages 0 10 0 3 2 2 4 Switch Slope Ramp speed for the switching process from large HP valve to small HP valve in...

Page 49: ...compressor Y N N 3 2 2 4 Oil Return Activation of the oil return function Y N Y 3 2 2 4 Dur Oil return Oil return time only visible if Acc Level Ctrl is set to YES 1 360 30 sec 3 2 2 4 Interval Interv...

Page 50: ...not fallen again due to the previously switched on ejector Evacuation mode The evacuation mode is activated when the accumulator level reaches the second highest level switch to empty the accumulator...

Page 51: ...1 Gas ejectors Operating mode Thresholds In the Thresholds operating mode the gas ejector stages are switched on and off when the control value of the small high pressure valve exceeds or falls below...

Page 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...

Page 53: ...he ejectors already switched on corresponds to the global opening degree of the high pressure valve exceeds or falls below the size of the next ejector stage by the differential value parameter Switch...

Page 54: ...the remaining liquid ejector stages are switched on after the waiting time has elapsed parameter Waiting time LE ON Number of liquid ejectors 3 number of accumulator sensors n max 4 Operating mode Hig...

Page 55: ...ing fixed speed fans and using a speed controlled fan The type of control can be set using the system centre the operator terminal or the LDSWin PC software Using the system centre or the operator ter...

Page 56: ...SIOX are then available for other functions Example Control of 12 ebm papst fans in two row gas cooler packages A as compared with 4 fans that are controlled via relays B here the basic module with 1...

Page 57: ...e of the individual fans in the gas cooler package in ascending order according to their serial numbers As the fans in the gas cooler package have a fixed physical position their switching sequence as...

Page 58: ...13 Switching order 4 becomes 2 5 SN JJWW000105 Modbus address 14 Switching order 5 becomes 3 6 SN JJWW000106 Modbus address 15 Switching order 6 becomes 3 7 SN JJWW000107 Modbus address 16 Switching...

Page 59: ...is set in menu 3 7 At the same time a second message is output in which an error status is transmitted This message is structured as follows Example message F yy A zz xxxxxxxx F fan yy switching orde...

Page 60: ...ned and a message is output This state is not permissible the fan must be disconnected from the power supply otherwise it will run with 80 of its capacity in emergency operation 0 fan is removed from...

Page 61: ...ss valve If the gas cooler of the refrigeration pack system can be bypassed using a gas cooler bypass valve 3 way valve the gas cooler temperature sensors tgk1 and tgk2 are positioned at different loc...

Page 62: ...r is withdrawn when the setpoint has been undercut and the speed Min speed starts with Min speed Offset The enable for the speed controller is withdrawn when the setpoint is undercut and the speed Min...

Page 63: ...time and variable switch on time While the control error is greater than 1 5 times the neutral zone the maximum switch on delay remains limited to 30 seconds If the control error is smaller than 1 5...

Page 64: ...the second half of the outputs actuates the delta operation G high speed A maximum of 6 fans can be controlled KKKG The fan motors are loaded or unloaded with all except the last relay stage With the...

Page 65: ...h speed delta operation When shifting down the capacity stages both fan outputs star and delta outputs are unloaded simultaneously The low speed is loaded again after a configurable time delay The fol...

Page 66: ...low speed Fans 1 2 low speed Fan 3 OFF Fan 1 low speed Fans 2 and 3 OFF All fans OFF The time delay for the switching from delta to star operation can be set using the parameter Del slow speed menu 3...

Page 67: ...er 1 Inactive speed controller enable for Min Speed 0 Function power supply bridging when tg Max and or tg Max WRG is exceeded The mains power operation is activated if the pressure has reached a spec...

Page 68: ...the controller A speed setpoint depending on the control error is calculated by a PI control algorithm which is activated on the speed controller via an analogue output 0 10 V The input signal for th...

Page 69: ...um speed 0 of the speed controller has been input using the parameter Min Drehzahl menu 3 2 2 1 the speed is reduced after a configurable time parameter B unlo T F1 menu 3 2 2 2 c to 0 using a ramp an...

Page 70: ...ositive control error the speed controller is enabled via the first capacity stage of the controller A speed setpoint depending on the control error is calculated by a PI control algorithm which is ac...

Page 71: ...meter Min Speed menu 3 2 2 1 the speed is reduced after a configurable time parameter B unlo T Fan 1 to 0 using a ramp and the fan output S1 is switched off Switching back from mains power operation t...

Page 72: ...1 2 3 4 or via the CAN bus from another pack controller in the system tG tG setpoint tG_max maximum tG setpoint tG_min maximum tG setpoint ta current outdoor temperature ta_max max outdoor temperature...

Page 73: ...used for switching to mains power operation In HRC mode the parameter tg Max HRC is used for this If HRC mode is active switching to mains power operation only takes place when the limit value tg Max...

Page 74: ...e kickstart and the next is implemented The kickstart is only performed for fault free motor cut out and enabled fans System Configuration menu 3 1 Control modes with an FC are executed at minimum spe...

Page 75: ...opening degree is determined using the PI controller Manual mode is reserved for test and service purposes and is not stored in the controller memory i e after a power failure controlled operation is...

Page 76: ...meter Description Input Defa ult Dim 3 2 3 MP Max Upper limit for MP HPV will be closed if exceeded 10 60 38 bar 3 2 3 dPm HP V Close P range for forced closing of the HPV in the case of exceeding the...

Page 77: ...ompressors Instead of conveying the refrigerant via a medium pressure valve from the medium pressure side to the intake side of the HP compressor it is more energy efficient with MP compressors to pum...

Page 78: ...MP compressor the MP compressors are controlled as combined control the first MP compressor is controlled with a frequency converter and the input signal for the frequency converter is calculated usi...

Page 79: ...ompressors Regulation No Parameter Menu Input Default Dim Description 1 Combined control 3 2 5 1 Combined control The following types of control are set here 1 step controller 2 combined control 2 p f...

Page 80: ...of capacity stages is adjusted according to the set Anz Verd Times can be set for maximum 2 stages 15 Basic unload time 3 2 5 2 3 250 S1 250 sec S2 250 sec s Basic time for unloading of the parallel c...

Page 81: ...alled if the cylinder temperature exceeds the set value Attention Cylinder head temperature sensors of the parallel compressors start directly after cylinder head temperature sensors of the NT compres...

Page 82: ...s water Air conditioning What this means for the refrigeration pack system and pack controller The heat on the high pressure side is discharged through heat exchangers As a result the utilisation of t...

Page 83: ...can have different behaviour in HRC mode HP setpoint HP valve regulation tG setpoint gas cooler outlet temperature regulation t0 setpoint low pressure regulation HP setpoint In controlled operation th...

Page 84: ...ered using the parameter HP Max HRC is used tG setpoint In HRC mode the setpoint for the regulation of the gas cooler outlet temperature can be specified as in normal operation or a fixed setpoint con...

Page 85: ...mode after the last deactivation Safety function against continuous activation and deactivation of the HR mode due to cycling request signal at the digital input or on the CAN bus 4 Verz St r WRG 3 2...

Page 86: ...transmitted via the CAN bus 13 to Min 3 2 2 3 50 10 C Minimum value for the to setpoint shift via temperature outside or CAN bus in HR mode The parameter is visible if the parameter to Schieb WRG is c...

Page 87: ...V1 08 11 2022 87 219 No Parameter Menu Entry Default Dim Description 20 Gask Drehz WP 3 2 2 3 0 100 Speed specification in HR mode when the heat pump is active gas cooler 100 bypassed For this functio...

Page 88: ...setting up refrigeration systems a distinction is made between normal and booster operation modes In normal operation the refrigeration circuits of different evaporator levels are operated in complet...

Page 89: ...he LT compressor control menu 3 2 6 parameter TK Freigabe set to Y Features of the LT compressor circuit Function Significance for the LT compressor circuit Setpoint toggle The toggle setpoint is perf...

Page 90: ...on of the FC actuating signal is performed using the PI controller Refer to the following table for the parameters for the configuration of the PI controller The setpoint for t0 can be configured sepa...

Page 91: ...tante XX K Max control error for variable switching times 1 15 2 K Standzeit S1 Minimum standstill time of the LT compressor with FC after shutdown 10 360 120 sec 5 10 3 LT compressor monitoring The f...

Page 92: ...ediately without taking their switch off times into account Parameters for monitoring of the LT compressors Menu Parameter Description Value range Default Dim 3 2 6 Motorsch Verd Enable for the motor...

Page 93: ...of the digital inputs 230 V AC 5 12 Monitoring In addition to control and regulation functions the following monitoring functions are integrated in the controller Safety chain Oil differential pressu...

Page 94: ...re selected signal priority is not sent and registered in the message memory until the delay time has elapsed However in order to ensure that any compressor HP fault is registered in the message list...

Page 95: ...ut available using menu 3 1 If the motor overload cut out is deactivated the parameter Motor protect Y N is not displayed and not evaluated The parameter Motor protect is activated at the factory For...

Page 96: ...nu 3 4 If the upper maximum value is exceeded the associated compressor is switched off and disabled for the following control processes after expiry of a configurable time delay menu 3 4 Comp temp de...

Page 97: ...rated in combined control the frequency converter is always enabled with the first compressor relay stage and the motor of the first compressor is controlled The following relay stage s is are used fo...

Page 98: ...omp up to 40 of the compressor output stages are disabled stage by stage until the pressure has dropped to a level below the limit value If all the compressors are switched on the first compressor is...

Page 99: ...gnal is not output in the case of measuring circuit errors of the HP transmitter The HP too low signal has no effects on the control and regulation processes 5 12 4 3 Monitoring of the HP Valve If the...

Page 100: ...loaded in the event of any medium pressure fault In the event of exceeding MP Off Comp there is an immediate step down to the specified number of compressors no return If the parameter Nr Comp MP Al i...

Page 101: ...an error message is logged in the fault memory The message is transmitted according to preselected priority The fan is enabled for the control when the contact is closed For some types of system the...

Page 102: ...e reached using the menu 3 3 Continuous control of a compressed gas cooler With a continuous control of the compressed gas cooler the superheat can be controlled even more precisely in addition to the...

Page 103: ...erature alternatively cylinder head temperature exceeds a configurable threshold value In order to prevent cycling of the valve hysteresis is provided difference downward from threshold value configur...

Page 104: ...rature Pt1000 input 9 terminals 25 26 SGI cyl head 3 3 50 180 C Threshold value for the enable of the valve for suction gas injection depending on the cylinder head temperature SGI difference 3 3 1 20...

Page 105: ...efault in the case of any measuring circuit error tgk1 is used see chapter Temperature sensors for regulation should be in a specific range during normal operation of the system Two limit values are u...

Page 106: ...n be switched on For example if the switching frequency is 10 switching operations per hour a compressor can be switched on at the earliest every 6 minutes Monitoring of the switching frequency The sw...

Page 107: ...Refrigerant Fill Level A rupture disk can be monitored using the digital input 22 terminals 92 93 of the controller or the maximum fill level of the refrigerant can be monitored via an additional leve...

Page 108: ...ts Neutral zone Control constant Switching times Humidity shift Gas cooler control maximum speed 5 14 Ambient Data for Setpoint Switching The factors used for the setpoint switching menu 3 1 room temp...

Page 109: ...controlled via the pack controller relay outputs The spray system can be configured in menu 3 2 5 The control of the spray system can be activated and deactivated using the parameter Spray System The...

Page 110: ...ain If the gas cooler outlet temperature falls below the switch on value S1 minus the specified hysteresis the first stage is switched off again As long as one stage of the spray system is switched on...

Page 111: ...linder head temperature sensor connection to the corresponding Pt1000 inputs 5 17 2 COP Optimisation Only for combined control where parameter M com out reg No see menu 3 2 1 1 The efficiency of the s...

Page 112: ...ation of the pack are recorded daily and stored with date menu 6 2 The data are archived in the pack controller for a period of 32 days and the display is shown in hours and minutes The switch on rate...

Page 113: ...is not authorised Furthermore it must be noted that the safety of the system or the installation in which the device is integrated is the responsibility of the creator of the system or installation If...

Page 114: ...of the SIOX extension module for ejector operation 4 Activation of ebm papst fans 5 Not used 6 and 7 Firmware update mode For details see chapter Default settings using S1 2 CAN bus address selector...

Page 115: ...ly cables and SIOX data cables see chapter Connector Pin Assignment for CAN Bus SIOX and Interfaces 6 2 1 1 Connecting the SIOX Modules to the Pack Controller The individual SIOX extension modules are...

Page 116: ...t be routed in the immediate proximity of high voltage or high frequency cables When routing the cables care must be taken to ensure that the minimum bending radius is complied with and that the cable...

Page 117: ...wer supply cables if necessary 6 2 2 Default settings using S1 Coding switch 1 setting DIP switch S1 coding switch 1 is not used DIP switch S1 Coding switch 1 Switch positions Pack type ON Not used OF...

Page 118: ...eration No ejector support Coding switch 4 setting DIP switch S1 coding switch 4 activates the control of the ebm papst fans via the Modbus DIP switch S1 Coding switch 4 Switch positions ON Control of...

Page 119: ...ee chapter Connector Pin Assignment for CAN Bus SIOX and Interfaces ATTENTION DIP switch S1 coding switches 6 and 7 may only be set to OFF for firmware update purposes In this state the controller wai...

Page 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...

Page 121: ...and Outputs The analogue inputs and outputs are configured as follows at the factory Analogue inputs 1 5 and 7 4 20 mA Analogue input 6 0 10 V Analogue outputs 1 4 0 10 V ATTENTION Reconfiguration of...

Page 122: ...IFE LED flashes for approximately 5 seconds after switching on For more details see chapter Status LEDs 6 2 7 1 Status LEDs DANGER Warning of dangerous electrical voltage Danger of electric shock BEFO...

Page 123: ...rd 5 LIFE green LED top Flashing Active lamp controller is supplied with power processor is running Off Power supply interrupted or device defective 6 POWER green LED bottom On Power supply OK Off Pow...

Page 124: ...V signal No comps number of compressor stages No cap stages number of capacity stages No cond stages number of condenser capacity stages Menu 3 3 Compressor monitoring t0 Comp OFF t0 limit value for...

Page 125: ...e inputs and outputs are sensitive to external supply and reverse polarity When connecting the pack controller to the control input of the FC speed controller the correct polarity must be strictly ens...

Page 126: ...mpressor or condenser control In the case of compressor combined control or fan speed control the fault signal outputs of the frequency converters speed controllers can be monitored For NT compressors...

Page 127: ...n is used which always follows the last used motor protection input For this type of control the message text for this input is automatically set to Speed controller HP Example number of fans n 3 Numb...

Page 128: ...5 56 The 0 10 V signal for the speed of the LT compressors is output via analogue output 1 of the basic module terminals 53 54 The 0 10 V signal for the speed of the parallel compressors MP compressor...

Page 129: ...power supply bridging is set instead B For fan combined control The relay output n 1 of the fan stages is used for bypassing the FC speed controller for fan combined control If the configurable tempe...

Page 130: ...xed speed compressors Compressor 1 and compressor 2 are alternately switched to the frequency converter for this using the configurable cycle time for the base load rotation The base load rotation of...

Page 131: ...ntroller and swap to RS485 if necessary b Note serial numbers of the fans and desired switching order 2 Modbus fan control activation a Switch on DIP switch 4 ON Modbus fan control activation Backup s...

Page 132: ...onfigured in the Switching Order menu For two row condenser gas cooler a number can also be allocated twice 3 Repeat in the case of error Proceed as follows if not all or no fans have been detected a...

Page 133: ...6 Battery Replacement No battery replacement for the controller by the user is envisaged as the battery service life is designed for greater than 10 years If the battery voltage message is displayed...

Page 134: ...nto a safe state as the shutdown of the controller during the firmware update can have undesired effects on the system component and or the system Caution data loss When changing the firmware version...

Page 135: ...The following steps must be strictly performed and observed during the firmware update 1 Strictly disconnect controller from the mains power supply there must be absence of voltage 2 Set DIP switch S...

Page 136: ...9 The following screen opens 7 Press Enter RETURN key The following screen opens 8 Now switch on the controller again Then start the download by pressing the Enter RETURN key The bar at the bottom ind...

Page 137: ...ller must be disconnected from the power supply for a short time after the firmware update ATTENTION In normal operation the coding switches 6 and 7 of the DIP switch S1 are always in the ON position...

Page 138: ...s on the basic module and the SIOX extension modules All connection cables from and to the controller with the exception of the digital inputs and the relay outputs must be shielded Otherwise malfunct...

Page 139: ...onnector Pin Assingments After connection of the power supply the LIFE LED flashes see chapter Status LEDs DANGER Warning of dangerous electrical voltage Danger of electric shock BEFORE connecting and...

Page 140: ...age Danger of electric shock BEFORE connecting and disconnecting it must be ensured that no voltage is present at all connections of the controller Wiring of the digital inputs All digital inputs of t...

Page 141: ...al block upper right at the back Terminal No Function Basic module N L PE 230 V AC power supply SUPPLY Neutral conductor phase 230 V AC PE ground conductor DANGER Warning of dangerous electrical volta...

Page 142: ...ned and easily accessible for the user and c must be labelled as a disconnecting device for the equipment 7 2 2 Terminal assignment of the 230 V AC digital inputs Connection On the basic module termin...

Page 143: ...or overload cutout compressor 3 LT MP motor overload cutout compressor 4 2 4 6 8 52 53 56 57 60 61 64 65 LT MP motor overload cutout compressor 5 LT MP motor overload cutout compressor 6 LT MP motor o...

Page 144: ...When HP combined control is active the digital inputs of the motor overload cutouts for the condenser fans can be used for monitoring the HP speed controller For parallel or stages combined control th...

Page 145: ...ay outputs Connection On the SIOX extension module terminal block upper left 8 relay outputs DANGER Warning about dangerous electrical voltage Danger of electric shock BEFORE connecting and disconnect...

Page 146: ...X ejector 1 2 3 4 5 6 7 8 15 16 18 25 26 28 35 36 38 45 46 48 13 14 23 24 33 34 43 44 Gas ejector 1 Gas ejector 2 Gas ejector 3 Gas ejector 4 Gas ejector 5 Liquid ejector 1 Gas ejector 6 Liquid ejecto...

Page 147: ...system components e g pressure transmitters Furthermore this will destroy the controller ATTENTION Malfunction due to interference All supply lines from and to the controller with the exception of the...

Page 148: ...36 37 Low pressure transmitter 24 V DC 4 20 mA GND 2 38 39 40 Retrieval of the high pressure valve HPV opening degree 24 V DC 4 20 mA GND 3 41 42 43 Low pressure transmitter Z2 24 V DC 4 20 mA GND 4 4...

Page 149: ...l supply lines from and to the controller with the exception of the 230 V power supply and signal cables must be shielded cable type LiYCY This particularly applies for the analogue inputs and outputs...

Page 150: ...only be performed when no voltage is present In the event of any mix up of the SIOX data cable RJ45 with an Ethernet network cable with PoE Power over Ethernet involved network devices can be damaged...

Page 151: ...power supply cable GROUND of 9 V 9 V DC GROUND of 24 V 24 V DC SHIELD 7 2 6 1 Terminal assignment of the Modbus analogue module 0 10 V DC The controller can be extended in each case by 4 analogue out...

Page 152: ...basic module to increase the inputs outputs e Configuration of the Modbus modules Terminal assignment of the Modbus analogue module Terminal No Function 0 10 V No MR AO4 1 1 C2 FC Medium pressure comp...

Page 153: ...Default even Parity is even odd Parity is odd none No parity is set Screen 5 3 1 b Configuration of the baud rate MODBUS ID XXXXX Description Input Default Dim 9600 Baud rate is 9600 Bd 19200 Baud rat...

Page 154: ...module to increase the inputs outputs Configuration of the Modbus modules Terminal assignment of the Modbus relay module Terminal No Function No MR DO4 1 11 C 14 N O 12 N C Valve for suction gas inje...

Page 155: ...fault even Parity is even odd Parity is odd none No parity is set Screen 5 3 1 b Configuration of the baud rate MODBUS ID XXXXX Description Input Default Dim 9600 Baud rate is 9600 Bd 19200 Baud rate...

Page 156: ...3 Rel Modul Diag Diagnostics menu for analysis of communication errors for the Metz modules MR DO4 MR DOA4 Menu 8 5 Service Mode Menu SERVICE ID XXXXX Description Input Default Dim 8 5 Modbus relays T...

Page 157: ...ted equipment is controlled as the software envisages O Manual OFF If any switch is in the 0 position the controller registers the logical MANUAL OPERATION OFF state The connected equipment is not con...

Page 158: ...ng additional symbols are displayed Display of the suction pressure trend Shows whether compressor capacity stages should be loaded unloaded or not switched after expiry of the delay times Display of...

Page 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...

Page 160: ...rminal The controller can be operated remotely e g from the machine room using the system centre a store computer or an operator terminal The communication with the controller is performed via the CAN...

Page 161: ...and CI 3x00 AL 300 1 CI 4x00 Alarms and messages button in the main menu for display of whether alarms are pending Alarms are acknowledged in the alarm list CI 3x00 AL 300 red LED signal lamps to ind...

Page 162: ...he E LDS component is called by entering the digits or selection of 3 1 2 via the remote control in the system centre store computer operator terminal or terminal device The menu item Remote control i...

Page 163: ...es e g the alarm list these can be paged through using the cursor buttons and In menus that provide more than 3 submenus these can be paged through using the cursor buttons and to display the remainin...

Page 164: ...error message is pending only store computer operator terminal is performed here 9 2 2 Call Controller Menu using Remote Operation Upper case and lower case can be toggled by tapping the MODE button I...

Page 165: ...r in the list that is then displayed using the cursor buttons and In the screen that opens the name position designation and the alarm priority of the controller can be input as required Step 3 The ma...

Page 166: ...omputer or operator terminal is only possible for controllers with CAN bus connection the deactivation of the input lock is then applicable for all components in the CAN bus system The lock down is au...

Page 167: ...ode For repair and maintenance work service personnel can deactivate the remote alarm function of the system centre and of the store computer for a limited period using the service mode 9 2 4 1 CI 4x0...

Page 168: ...buttons MODE and ENTER simultaneously to open the screen for the suppression of the remote alarm signalling and input the service mode duration 1 255 minutes The service mode is now activated for the...

Page 169: ...lues 1 2 Actual values 2 ACT VALUES Analogue values 2 1 ANALOGUE VAL Cyl temp 2 1 a ANALOGUE VAL PC Cyl Temp 2 1 b ANALOGUE VAL LT Cyl temp 2 1 c ANALOGUE VAL Compressor 2 2 COMPRESSOR I0 Condenser fa...

Page 170: ...elete 5 2 MESSAGE Modbus 5 3 MODBUS Configuration 5 3 1 MODBUS Diagnose 5 3 2 MODBUS Rel Modul Diag 5 3 3 DIAGNOSE ebm Diagnose 5 3 4 DIAGNOSE 6 Operating data 6 OP DATA Operating hours 6 1 OP DATA Co...

Page 171: ...tings Continue to menu 7 8 Service Mode Continue to menu 8 10 1 2 Menu 1 Summary Act to XXX C Evaporation temperature actual values LP Setp to D N XXX C Calculated t0 setpoint LP evaporation temperatu...

Page 172: ...ariable for compressor speed in percent only visible when no min and max FC frequencies are entered 100 corresponds to 10 V at the analogue output Comp Speed OH Currently transmitted control variable...

Page 173: ...ison Comp Speed LT XX Z2 compressor speed Suctiongas LT X X C Current Z2 suction gas temperature Superheat Z2 X X K Current superheat Z2 HR setpoint X Analogue input for HR setpoint shift only visible...

Page 174: ...pacity stage 3 relay output depending on the configuration and compressor type the number of the displayed capacity stages is for NT and parallel compressors with basic module 1 max 4 for NT and paral...

Page 175: ...a CAN bus Cons enab Rel XXX Consumer enable relay output toggle Comp XXX Status of relay output for FC compressor base load rotation for compressor combined control only visible if compressor combined...

Page 176: ...Refrigerant R744 Refrigerant R744 CO2 R744 Sensor match Matching of the pressure transmitters Screen 3 1 a Sensor match No comps XX Entry of the number of compressors 1 4 8 3 3 Diff comp X Unequal com...

Page 177: ...Mot prot PC Enable parallel compressor motor overload cutout YES NO Y N N Oil HP cont PC Oil pressure difference switch HP switch parallel compressor YES NO Y N N No cond stages X Number of condenser...

Page 178: ...lection of signal interface pressure transmitter LP Z2 4 20 mA or 0 10 V Screen 3 1 a d LP Z2 Min XXXb Pressure for 4 mA or 0 V at output of LP Z2 pressure sensor LT 0 2 0 1 0 bar LP Z2 max XXXb Press...

Page 179: ...ENABL COMP ID XXXXX Description Input Default Dim Comp stage 1 XXX Capacity stage 1 ON OFF ON Only the available capacity stages depending on configuration are displayed Comp stage 8 XXX Capacity sta...

Page 180: ...Comp Contr Continue to menu 3 2 6 Menu 3 2 1 LP control LP Control ID XXXXX Description 1 Compressor control Continue to menu 3 2 1 1 2 to adjustment Continue to menu 3 2 1 2 3 LP Control day Continue...

Page 181: ...z MinFreq FC Hz Scaling of the analogue output for the compressor speed Here the frequency transmitted by the FC at a control variable of 0V is set This setting must correspond to the value set on the...

Page 182: ...a to Ramp K Min XXX The to setpoint shift can be subjected to a ramp The ramp is inactive for For to adjustment via analogue input 6 or via the CAN bus a ramp speed of 1 K min is active 1 20 K Min Max...

Page 183: ...witching hysteresis for step control only visible for step control type of control 1 10 4 K NZ speed con 0K Dead band for the loading and unloading of fixed speed compressors during combined control o...

Page 184: ...3 250 60 sec V UNLO T S4 XXX s 3 250 80 sec V UNLO T S5 XXX s 3 250 100 sec V UNLO T S6 XXX s 3 250 120 sec V UNLO T SN XXX s 3 250 120 sec Basic module 1 max 4 capacity stages with first SIOX extens...

Page 185: ...ec B LOAD T S4 XXX s 3 250 250 sec B LOAD T SN XXX s 3 250 250 sec Basic module 1 max 4 capacity stages with first SIOX extension module 1 max 8 capacity stages Screen 3 2 1 4 b Variable time capacity...

Page 186: ...ge see chapter Gas cooler package with ebm papst fans Screen 3 2 2 1 b EBM Manual Run To the submenu for the manual operation of the fans Screen 3 2 2 1 c Min Drehzahl XXX Min fan speed only visible i...

Page 187: ...ES NO Y N N Fan X OFF by al X Switch off fans when motor overload cutout is tripped YES NO Y N Y Fan Kickstart X For activating the kickstart function for the fans Y N N Fan Offtime Standstill time of...

Page 188: ...nnected from the power supply otherwise it will run with 80 of its capacity in emergency operation 0 fan is removed from the switching order list only possible if authorisation Master Example 01010001...

Page 189: ...rature 10 50 28 C tod max XX C Max outdoor temperature for setpoint shift 16 48 26 C Gl ttung tG XX C Smoothing factor for the measurement of the gas cooler temperature 1 20 12 tG Offset N XX K tG off...

Page 190: ...100 15 min Max Regabw HD Xb Maximum permissible control error in the HP circuit The function is deactivated with input of 0 30 5 b VzgMax Rabw HD Xm Delay time after which a fault message is generate...

Page 191: ...ic module 1 max 4 capacity stages with first SIOX extension module 1 max 8 capacity stages Screen 3 2 2 2 d Variable time for condenser capacity stages OFF V UNLO T ID XXXXX Description Input Default...

Page 192: ...2 3 b to Min Minimum value for the to setpoint shift via temperature outside or CAN bus in HR mode The parameter is visible if the parameter to shift HR is configured to Outdoor temp or CAN BUS The t...

Page 193: ...or switching on the next largest ejector stage only visible in the Thresholds operating mode 0 100 70 Threshold Off Min threshold of the small HP valve for switching on the previous smaller ejector st...

Page 194: ...2 min Superheat Threshold of the superheat when oil return is active only visible if Acc Level Ctrl is set to NO 3 20 10 K Screen 3 2 2 4 a Operation Mode OPERAT M ID XXXXX Description Input Default...

Page 195: ...m SPRAY ID XXXXX Description Input Default Dim Spray System X Activation of spray system Y N Y N N Nachtbetrieb X Spray system active in night operation Y N Y N N Temp S1 Min XX C Gas cooler outlet te...

Page 196: ...pressor can be enabled 0 100 30 EnableTime 1 XX s Delay time 1 time during which the MP valve must have a specified opening degree before MP compressors are enabled 0 600 30 s EnableLimit 2 X Limit va...

Page 197: ...of the variable times tv ON Basic unload time OFF Display basic times tb OFF Vari Z LeiStu OFF Display of the variable times tv OFF Off Time S1 Minimum standstill time of the LT FC compressor after sh...

Page 198: ...b MP limit value for compressor shutdown 10 0 62 0 40 0 b MD EIN Verd XXX b MP limit value for compressor enable 36 37 5 35 0 b Anz Verd MD Al XXX b Number of running compressors at MP alarm 1 12 MD z...

Page 199: ...is subtracted in each case from SGI hot gas and SGI cyl head 1 20 5 K SGI overh high XX K Threshold value for the enable of the suction gas injection valve depending on too high suction gas superheat...

Page 200: ...sure cutout tripped 0 99 1 LP cutout X Low pressure cutout tripped 0 99 2 Low LP X Lower threshold t0 undercut 0 99 2 High HP X Upper threshold tc exceeded 0 99 2 Messkreis Zyl X Fault in cylinder hea...

Page 201: ...erheat X Suction gas superheat too low 0 99 0 Deviation MP X MP control error too large 0 99 0 NT Cascade X NT controller not accessible or faulty 0 99 2 Meas err LP Z2 X Error in low pressure Z2 meas...

Page 202: ...N 0 99 2 Manual OFF LT X LT compressor manual control switch OFF 0 99 2 M err Suct gas LT X Error in the LT compressor measuring circuit 0 99 2 Low Superheat LT X LT circuit low superheat 0 99 2 LT Cy...

Page 203: ...ge COND MON ID XXXXX Description Input Default Dim Av at dT 0 X XX Average value for delta T at 0 Kelvin Av at dT 30 X XX Average value for delta T at 30 Kelvin Screen 3 9 d Utilisation frequency COND...

Page 204: ...t savg X Automatic summer winter time changeover YES NO Y N Y Screen 4 b Changeover times UMSCHALTNGPOS XXXXX Description Input Default dimension dd hh mm dd hh mm Entry in each case of up to 7 change...

Page 205: ...tion Input Default Dim 9600 baudrate is 9600 Bd 19200 baudrate is 19200 Bd Menu 5 3 2 Modbus diagnostic is not described here Menu 5 3 3 Rel Modul Diag for diagnosis of the connection of Modbus module...

Page 206: ...time Continue to menu 6 1 2 History Continue to menu 6 2 Menu 6 1 Display of the operating hours OP DATA POS XXXXX Description 1 Compressor Continue to menu 6 1 1 2 Condenser fan Continue to menu 6 1...

Page 207: ...ontinue to menu 6 2 3 4 PC run times Continue to menu 6 2 4 5 PC starts Continue to menu 6 2 5 6 PC Activity Continue to menu 6 2 6 7 LT Run times Continue to menu 6 2 7 8 LT comp starts Continue to m...

Page 208: ...yed compressor stages depends on compressor type and expansion stage as follows for NT and Parallel Compressors with Basic module 1 max 4 for NT and Parallel Compressors with first SIOX extension modu...

Page 209: ...ernal analogue output 4 terminal 4 of the Modbus analogue module 0 0 10 0 0 00 V Menu 8 2 Compressor defaults ON OFF SERVICE ID XXXXX Description Input Default Dim Comp stage 1 XXX Switching state of...

Page 210: ...XXX Switching state of the respective relay output of the Modbus relay module ON or OFF ON OFF OFF Relay 8 XXX ON OFF OFF Menu 8 7 Ejectors SERVICE ID XXXXX Description Input Default Dim Output E 1 X...

Page 211: ...dispose of electrical and electronic waste in compliance with the statutory regulations based on the Directive 2012 19 EU of the European Parliament on waste electrical and electronic equipment This d...

Page 212: ...rity number in each group 9 19 29 99 is reserved for low priority alarms which should only generate local alarm signalling e g open cold room door All other priority numbers are designed for low prior...

Page 213: ...until approx 50 of all available compressor capacity stages are in operation A switching process is performed after expiry of the basic time The variable times are not taken into account In the event...

Page 214: ...157 High Cyl temp Cx Cylinder head temperature for compressor Cx upper limit value exceeded High Cyl temp LT x Cylinder head temperature for LT compressor Cx upper limit value exceeded 160 HP cutout...

Page 215: ...x Compressor stage x has been automatically locked 5x cylinder temperature too high per day 219 Meas error MP Error in the measuring circuit for measurement of the medium pressure 220 MeasErr gas out...

Page 216: ...0 ohm 1 x 0 10 V Analogue outputs 1 4 x 0 10 V 4 20 mA 0 10 V load min 1 k 4 20 mA resistance max 800 ohm 1 Supply cables to analogue inputs outputs must be shielded Basic module SIOX extension module...

Page 217: ...ccording to DIN EN 60068 2 27 Transport and operation 30 g Vibration 10 150 Hz according to DIN EN 60068 2 6 Transport and operation 2 g Atmospheric pressure Transport 660 hPa 1060 hPa Operation 860 h...

Page 218: ...Firmware V1 41 V1 08 11 2022 218 219 13 3 Mechanical Data SIOX Extension Module SIOX extension module with manual control switch all dimensions in mm 1 mating connector and cable...

Page 219: ...e sensor 4 wire Pt1000 for wall mounting KGLZPT1000 Modbus analoque module Set Modbus module with 4 analogue outputs 0 10 V DC incl 2 x 100 Ohm and terminal MODBAOUTPV Modbus relay module Modbus relay...