Firmware V1.41 V1
08.11.2022
33/219
Parametrisation
Parameter
Menu
Value range
Default
Unit
Description
Qo assignment
3-2-1-1
YES / NO
NO
-
Parameter to assign an output to the
compressors. If NO, all compressors are
assumed to be the same size.
ASSIGN Qo
3-2-1-1
Submenu
-
-
Submenu in which a coefficient of
performance is assigned to each
compressor - the submenu is only visible if
the "
Qo assignment
" parameter is set to
YES.
The following points must be observed:
- Input of the percentage proportion
between 5..100%
- The total capacity of all compressors must
not exceed 100%; any input (sum) of more
than 100% is not possible!
- The coefficient of performance for each
compressor must have been calculated for
50 Hz.
BaseLoadRot.FC
3-5
YES / NO
NO
-
Activation of the FC BL rotation. This
parameter must be set to NO so that
compressors with different sizes can be
controlled.
No.cap.stages
3-1
1...3
1
-
Configuration of the compressor stages.
This parameter must be set to 1 so that
compressors with different sizes can be
controlled.