Firmware V1.41 V1
08.11.2022
88/219
5.10 LT compressor in booster mode
In addition to the regulation of the transcritical CO
2
refrigeration circuit, it is possible to control
LT compressors
in booster mode
with only one controller.
When setting up refrigeration systems, a distinction is made between normal and booster operation modes. In
normal operation, the refrigeration circuits of different evaporator levels are operated in completely independent
systems.
Each circuit has a compressor set, a condenser set and connected refrigeration points However, in booster
operation, the various circuits are operated with only one condenser set and therefore with only one common