26
Program menu
PROGRAM
To be able to measure the temperature as accurately as possible, there are two
temperature ranges, one from -15 °C to +75 °C and one from 0 °C to +150 °C.
There is also a frost protection program to enable sensitive installations to be
safeguarded against frost in a simple manner.
The low temperature and frost programs are in the
MAIN MENU
under
PROGRAM
.
To change program, browse using
or
and select with
. The low temperature
program is set at the factory.
The high temperature sensor (see below) must be connected and activated to
activate the high temperature program. If the high temperature sensor is not
activated in the start menu, it can be activated from the
MAIN MENU
under
SYSTEM
and
SENSOR
; here select
B: HIGH TEMP
.
IMPORTANT
– The sensor that is provided with EB Therm 800 is intended for the
low temperature and frost protection program, and must not be used with the high
temperature program. The sensor for the high temperature program is not included
in the package, but must be ordered separately; it has part number E 85 816 73.
Only one high temperature sensor can be connected. It must always be connected
as B, terminal block 7 and 8.
Low temperature program
LOW TEMP
This program limits the temperature range to between -15 °C and +75 °C. This
program is provided for two reasons, partly to minimise the risk of the wrong
sensor being used, which would damage the installation, and because the different
temperature ranges demand sensors with different characteristics.
Select the lower temperature range in the
MAIN MENU
under
PROGRAM
and
LOW
TEMP
. This program is preselected but can be changed to the frost protection or
high temperature program at any time.
Frost protection program
FROST PRO
The program is intended for the frost protection of installations or pipes and limits
the settable temperature range to between -10 °C and +15 °C. The values can be set
with an accuracy of 0.5 degrees and the factory setting is +5 °C.
Select the program in the
MAIN MENU
under
PROGRAM
and
FROST PRO
. It is pre-
selected but can be changed to the frost protection or high temperature program
at any time.
High temperature program
HIGH TEMP
This program limits the temperature range to between 0 °C and +150 °C. This
program is provided for two reasons, partly to minimise the risk of the wrong
sensor being used, which would damage the installation, and because the different
temperature ranges demand sensors with different characteristics.