40
XSTORAGE HOME 3P INSTALLATION MANUAL
MN700009EN August 2020 www.eaton.com
00 Title
See the connection instructions shown in
Figure 7
.
Make sure to be compliant with the local regulations.
Make sure to be compliant with the grid code of the distribution network operator.
For safety reasons, an appropriately rated input load disconnector (20 A) must be provided for each individual
xStorage Home 3P. No load should be connected directly to the xStorage Home 3P inverter.
The power losses on the AC GRID line must be less than 1% of the rated power. The indicative data of the
connection are reported below:
The connection of multiple inverters to the public grid must comply with current legislation relating to
maximum power imbalance.
Before starting the connection operations, make sure that the external AC line main switch is disconnected
and that the AC GRID and EPS circuit breakers are disconnected.
Do not carry out other operations on the inverter for at least 10 minutes. The inverter contains capacitors
that need a minimum time to discharge.
Before starting the connection operations, make sure that the DC line switch is off.
Remove the cover of the connection compartment by removing the screws as shown in
Figure 7
.
Before starting the connection operations, make sure that the ON/OFF switch is in the “0” position.
6.3 AC grid Connection
Wire cross-
section
Line maximum length
XSTH3P050P075V01
XSTH3P060P090V01
XSTH3P080P120V01
XSTH3P100P150V01
2.5 mm
2
18 m
12 m
4.0 mm
2
29 m
19 m
6.0 mm
2
45 m
30 m