Technical Data
PR211-183-505-01
VoCALL CFVCCM9 compact master
EATON
www.eaton.com
Technical specification
Technical specification
Product description
VoCALL Compact 9 Line Master Unit
VoCall 10 Line Slave Exchange Unit
Power supply
Volatge
230V ac +/- 10% 50/60Hz
Internal power supply
14V dc
Supply and battery
Monitored, open, short, fuses
Protection
Deep discharge, short, thermal
Battery size and type
1 x 12V VRSLA (5Ah required)
Mains fuse
240V 2A HRC
Battery fuse
250A PTC
Charge current
250mA
Inputs
Number of lines
9
10
Remote enable
Short to use
N/A
Outputs
Number
2 (fault & in-use)
N/A
Type
Volt free relay
N/A
Contact
30V dc 1A
N/A
Controls
Buttons
4 navigation keys
N/A
Display
4 lines, 20 characters
N/A
Status LEDs
3 (healthy, call & supply)
1 supply
Fault LEDs
3 (line, PSU & general)
1 general
Outstation cables
Type
Enhanced
Cores
2 Core (1mm or 1.5mm) Fire rated enhanced (standard fire rated cable can be used is certain
circumstances - see VoCALL wiring guide)
Distance
500m
Network cables (for use with the 10 line slave unit)
Type
Enhanced
Cores
1 off 4 core (1mm CSA Soft Skin)
Distance
10m (max) must be within fire barrier for compliance with current standards
Physical
Contruction
Powder Coated Zintec
Weight
6.5kg
4.8kg
Installation
Mounting
Surface or semi-recessed
Surface
Cutout
330mm x 300mm (semi-recessed unit)
N/A
Cable entries
Top: 17 x Cable knockouts (20mm)