Summary of Contents for VoCALL CFVCCM9 compact master

Page 1: ...ce Communications System EVCS is designed to fully comply with BS5839 Part 9 2011 abb Pt9 for use as a fire telephone system disabled refuge call system or as a combined system when both fire telephon...

Page 2: ...und a site it is essential all units are on the same mains phase as they are classified TEN 230V powering from different phases can mean a 440V potential can be present in a unit during a major fault...

Page 3: ...incoming mains Mains SHOULD NOT enter the box by any other hole If additional holes are required then the can be drilled as shown below taking care not to obscure the battery or PCB locations Unused...

Page 4: ...pact unit and outstations Following the publication of BS5839pt9 2011 the guidance on cables for the VoCALL Compact unit has changed following a relaxation in the requirements of the standard Type A o...

Page 5: ...ne Connector on Network Compact unit toYellow phone lead Hands free refuge point Type B Connections inside the Network Compact unit Line Connector on Network Compact unit toType B line Line Connector...

Page 6: ...Set Site Name Menu The second line can be changed from Set Panel Name Menu The third line contains the status of the unit The fourth line shows the current time and date The padlock in the top right...

Page 7: ...Missing outstation 4 Scroll through the root menu using the navigation keys until View current fault is selected Press TICK to enter the View current fault menu Use the navigation keys to scroll thro...

Page 8: ...een Use the navigation keys to select Next Save or Quit as desired then press TICK Both Save and Quit will go back to the root menu Change engineer PIN The default Engineer PIN to access the configura...

Page 9: ...n Set panel name Compact M9 Next The current master name will be displayed on screen with the cursor on the first character Use the navigation keys to scroll to the correct character then press TICK R...

Page 10: ...th a symbol Select outstation S10 outstation 10 Back M9 Outstation 1 Unlocked this outstation exists Line through circle this outstation does not exist or is in fault Select the outstation to be confi...

Page 11: ...uttons connected using the TICK key or if already connected placed on hold using the TICK key a second time If the CFVCCM9 master handset wishes to ring an outstation they may do this by scrolling thr...

Page 12: ...free relay N A Contact 30V dc 1A N A Controls Buttons 4 navigation keys N A Display 4 lines 20 characters N A Status LEDs 3 healthy call supply 1 supply Fault LEDs 3 line PSU general 1 general Outsta...

Page 13: ...de la Longeraie 7 1110 Morges Switzerland Eaton eu 2018 Eaton All Rights Reserved Publication No PR211 183 505 01 CSSC 930 February 2018 Eaton is a registered trademark All other trademarks are proper...