2 Installation
2.2 Activating the bus termination resistor for PROFIBUS-DP
12
SmartWire-DT Gateway EU5C-SWD-DP
01/13 MN120001Z-EN
www.eaton.eu
Figure 4:
Setting the field bus address on an EU5C-SWD-DP gateway
2.2 Activating the bus termination resistor for PROFIBUS-DP
If the EU5C-SWD-DP gateway is the first or last field bus module, a bus ter-
mination resistor must be connected externally. This resistor can either be a
separate bus termination resistor or a special D-sub plug with an integrated
bus termination resistor, e.g., ZB4-209-DS2. This plug has an integrated bus
termination resistor that can be enabled and disabled.
2.3 Mounting Considerations
Install the EU5C-SWD-DP gateway in a control cabinet, a panelboard, or an
enclosure in such a way that the power supply and terminal connections can-
not be touched accidentally during operation. Snap the device onto an IEC/
EN 60715 top-hat rail or fix it in place using fixing brackets. EU5C-SWD-DP
gateways can be mounted either vertically or horizontally.
For ease of wiring, leave a clearance of at least 3 cm between the device ter-
minals and the wall or adjacent devices.
EU5C-SWD-DP
Example: Address 18
dec
OFF
ON
2 3 4 5 6 7 8
1
1
2
4
8
16
32
64
OFF
ON
2 3 4 5 6 7 8
1
Figure 5:
Vertical mounting
Figure 6:
Horizontal mounting
30 mm
(1.18”)
30 mm
(1.18”)
30 mm
(1.18”)
30 mm
(1.18”)