4.2.6 Features
Use joy-stick to access “Features” menu where you can
enable or disable additional system features like:
1. BBM (Battery Block Monitoring)
2. Remote Panel
BBM (Battery Block Monitoring)
Battery Block Monitoring function is always enabled.
Sealed batteries in accordance with EN 60896-2 provide
the energy to operate the emergency lighting in the event
of a power failure in the general 230V mains supply. Dur-
ing normal operations SelvGuard device monitors the state
of the batteries and if required it recharges them gently.
On the controller board, there is built in capability for bat-
tery monitoring which measures and displays individual
battery voltage in addition to current and battery compart-
ment temperature. With this, you can measure individual
battery voltage so you can timely detect a fault in the bat-
tery string. This allows you to reduce maintenance time
and cost.
The battery is connected to the controller board via a bat-
tery disconnector mounted on the DIN rail (6mm² -10mm²).
The battery leads are each led through an ISO gland (PG
gland) into the battery compartment.
SelvGuard was developed and manufactured in conformity
with the following EC guidelines:
• Low Voltage Directive 2006/95/EC
• Guideline 2004/108/EC on electromagnetic compatibility
Details on the national (DIN), European (EN) and inter-
national (IEC) norms that must be complied with can be
found in the CE conformity declaration for the device.
Main menu
Monitor
System info
TestTest
Faults and Events
Config Parameters
Features
Display settings
Features
BBM
Remote Panel
Back
OK
Cancel
Back
OK
Cancel
Back
OK
Cancel
Back
OK
Cancel
BBM
Enable
Faults and Events
Active Fault
Fault Log
Event Log
BBM Log
BBM Log (1/10)
49.7 V
-0.9 A
B1 12.2 V B2 12.4 V
B3 12.3 V B4 12.8 V
+32°C
10:25:02
4.2.6 Features