16
CEAG Remote Display for Central Power Supply Systems
40071860348 October 2019 www.ceag.de
Relay Output
Relay
1
Mains fault
Charge fault
CKT fault
Common Sys Fault *
Deep Discharge ACK
Relay
1
Relay
2
Relay
3
Relay Output Screen
Relay
1
Mains On
Mains faults
*
Charge Fault
*
CKT Fault
*
Common Sys Fault
Deep Discharge ACK
Back
OK
Cancel
Back
OK
Cancel
Date and Time
DD MM YY hh:mm:ss
02
.07.19 08:32:49
System Power
System Power
1200 W
Batt. Capacity
50.00 Ah
Rated Duration
01:00 Hrs
Relay Outputs
Use joy-stick to access “Relay Outputs” menu where you
can configure relay outputs functionality:
• Mains On
• Mains Fault
• Charge Fault
• CKT Fault (Circuit fault)
• Common Sys Fault (Charger Fault or CKT Fault)
• Deep Discharge ACK
• Function Test
• Batt. Duration Test
Relay outputs are used for remote signal or to integrate
with BMS.
Use Joy-stick to select Relay number (1, 2 or 3). After
selecting relay number, select which functions should be
signalized via the respective relay. More than one function
can be attributed to one relay output. ‘Mains Fault’ and
‘Mains On’ cannot be attributed to one relay simultaneous-
ly. A * will appear to mark the selected functios. In right
screen for example, Relay 1 is used to signalize: Mains
Faults, Charge Fault or Circuit Fault (CKT Fault).To save
configuration follow same steps as in previous section.
Date and Time
Use joy-stick to access “Date and Time” menu where you
can edit time and date settings.
Move cursor over the field you want to chanve and when
cursor starts blinking, use joy-stick up and down to incre-
ment / decrement the value. To come out of editing press
joy-stick.
To save configuration follow same steps as in previous
section.
System Power
Use joy-tick to access “System Power” menu where you
can edit the power output of you LPS. Do this if you want
to configure your system to have bigger runtime than 1
hour. Check discharge information provided in chapter
3.3.4 Connecting the batteries from SelvGuard installation
manual. After you have selected System Power, you shall
also select the desired runtime, according to the discharge
table in chapter 3.3.4 Connecting the batteries from
SelvGuard installation manual or according to the battery
discharge parameters (in case you use other batteries than
originally supplied).
You can select between:
• 1-283 for a 300W system, default 283
• 1-600 for a 600W system, default 600
• 1-900 for a 900W system, default 900
• 1-1200 for a 1200W system, default 1200
Relay Outputs