17
CEAG Remote Display for Central Power Supply Systems
40071860348 October 2019 www.ceag.de
NOTE
*Values will not switch to default if previously changed.
(e.g. if a 283W system was set to 3h@126W, it will stay
the same after factory reset)
For more information, consult SelvGuard installation man-
ual, chapter 6.2.5 Config Parameters - Factory Defaults.
Factory Defaults
Set to Def Settings?
Press Enter to confirm
or press
Left key to Cancel
Factory Defaults
Use joy-stick to access “Factory Defaults” menu where
you can set all parameters to default values. Press on joy-
stick and a pop-up message will appear and ask for confor-
mation (to avoid loss of parametrization due to accidental
selection). Press joy-stick again for validation or select
cancel if you want to skip.
To see defaults parameters list, check SelvGuard instal-
lation manual, chapter 6.2.5 Config Parameters - Factory
Defaults.
After 2-3 seconds it will switch to Home Screen.
Pop up message
Back
OK
Cancel
Back
OK
Cancel
Extended Emergency
In this section Admin can adjust Delay On Mains Return
features: Manual / Automatic and Duration time. Delay On
Mains Return represents the duration after non-maintained
lights are turned off when mains returns.
If 'Manual' is selected, then only Admin can turn-off non-
maintained lights after mains return via local display (see
section 4.2.2 Block and Reset Alarm) or via Optional Input
(Manual Reset function).
NOTE
If we configure Optional Input to Manual Reset, then oper-
ation of Extended Emergency feature will be automatically
forced to 'Manual'.
Admin can adjust the delay time from 1 min to 99 min, in
steps of minutes.
Extended Emergency