14
CEAG Remote Display for Central Power Supply Systems
40071860348 October 2019 www.ceag.de
Maintained
Non Maintained
Circuit Setup
Use joy-stsick to access “Circuit Setup” menu where you
can select between maintained or non-maintained func-
tionality for each individual End circuit group
(Output1 / Output2):
Output1 (consisting by default of circuits 1 to 6) and
Output2 (consisting by default of circuits 7 and 8). The
Outputs can be triggered via:
• LCD display or
• Remote display
By default, both Outputs are set to “Maintained” mode.
Move cursor to “OK” button and press joy-stick to save
changes and go back to previous menu; alternately move
cursor to “Cancel” button and press joy-stick to go back
to previous screen without saving.
Optional Input
Use joy-stick to access “Optional Input” menu where
you can select „Z Inputs” functionality. Together with “Z
Inputs” functionality you need to select how this function-
ality will be triggered:
Level trigger:
Edge trigger:
Available functions:
Optional input
functions
Edge
Trigger
Level
Trigger
1
No Function
(Default)
-
-
2
Output1 (O1)
3
Output2 (O2)
4
FT start
5
DT start
6
Cancel FT DT
7
Manual reset
8
Deep
Discharge Ack
9
Ventilator Monitor
NOTE
No function is pre-configured by default in “Optional
Input” menu.
To save configuration follow same steps as in previous
section.
Optional Input
Opt In1 (Z1)
FT start
Z1 - I/P trigger
Edge
Opt In2 (Z2)
No function
Z2 - I/P trigger
Optional Input
Opt In1 (Z1)
Inhibit
Z1 - I/P trigger
Edge
Opt In2 (Z2)
No function
Z2 - I/P trigger
Ventilator Monitor
Deep Discharge Ack
Manual reset
Cancel FT/DT
DT start
FT start
Output 2 (O2)
Output 1 (O1)
No function
Edge
Level
Circuit Setup
Output 1
Maintained
Output 2
Non Maintained
Back
OK
Cancel
Back
OK
Cancel
t > 1s
t > 100ms
Circuit Setup