CEAG Remote Display for Central Power Supply Systems
40071860348 October 2019 www.ceag.de
4.1.4 Login
This screen is used to select different access levels, e.g. Ad-
min or User. At first start-up User is deactivated. User can be
activated / deactivated when logged in as Admin from 6.2 Ad-
min main menu - Manage account.
The default password for Admin is 111111. The default pass-
word for User is 222222.
ATENTION
If the password is lost then follow the instructions mentioned
in Recover Password section.
NOTE
For enhanced safety of the system we recommend you to
change default password.
To change password, please follow instructions described in
chapter "4.2.5 Config Parameters". Change password
Admin Login and its Main Menu
In main menu screen press on Login option. It will switch in to
login screen. Select “Admin”.
After successful login, Main Menu will show additional sub-
menus like below.
User Login and its Main Menu
If User is activated, you can login as User from Login menu.
To recover User password, enter Recover Password menu, go
to User and then enter Admin password. you'll be prompted to
select new user password.
Main menu
Monitor
System Info
Language
Login
Back
OK
Cancel
Login
Admin
User
Recover Password
Back
OK
Cancel
Admin vs. User
Menu Items
Admin
User
No login
Monitor
Test
Faults and Events
Config Parameters
Features
Display Settings
System Info
Block and Reset Alarm
Language
Manage Account
Login/Logout
4.1.4 Login