System Options Menu
Page 53
Confirmed Alarm Output Types
The following output types are available:
Confirmed Alarm (page 39)
– Generated when there is a confirmed alarm.
Burg Confirmed Alarm
– Generated when any two of the following alarms have
activated (in any order) while the system is set (subject to the entry timer not
expiring, as described above):
Normal Alarm
24 Hour Alarm
Entry Route
Tamper (this must be on a different zone from the other alarm)
The two alarms must occur within the
Confirmation Time
.
HUA Confirmed Alarm (operates only when BS8243 is enabled)
– Generated when
users have activated two separate Hold Up Devices (HUDs), or an HUD and tamper
(in either order). For an HUD and tamper, the tamper must be on a different zone
from the HUD alarm. The two alarms must occur within the
HUA
Confirm Time.
Note:
A confirmed alarm is communicated only when the
Alarm Response
is set to
Siren+Comms (see page 46).
Confirmation Time
This is available only when
Confirmation Mode
is set to DD243 or BS8243.
The option determines the length of the confirmation time for Burg Confirmed Alarms. You
can select any time between 1 and 60 minutes. Confirmation times less than 30 minutes
do not comply with BS8243 or DD243.
Entry Alarm Delay
Use this option to determine what the system will do if a user strays from an Entry Route
zone during entry. (This option is available to provide compliance with EN 50131-1.)
Disabled
Makes the system give an alarm immediately a user triggers a zone other than the
entry route zone during entry.
Note:
This is not compliant with EN50131.
Enabled
If the user triggers a zone other than the entry route zone during entry, the system
waits 30 seconds before raising a full alarm. The system also gives an internal alarm
during the 30-second wait.
If the user enters an access code or presents a tag before the end of the 30-second
period, the user can reset the system.
After Entry
This is available only when
Confirmation Mode
is set to DD243 or BS8243.
Never
The control unit turns alarm confirmation off if the user enters by the entry door (used
for DD243:2004 clauses 6.4.2 and 6.4.4 and BS8243:2010).