Settings Options Menu
Page 46
Exit Time
This option is available only if
Exit Mode
is set to Timed Set or Silent Set. The exit time
can take any value between 10s and 120s.
Entry Time
The entry time can take any value between 10s and 120s. The entry time you select in this
option applies to full set and all part sets.
To comply with EN50131-1 Clause 8.3.8.2, maximum is 45s for Entry Time.
Extended Entry Time
This defines the entry time for Final Exit zone types that have the
Extended Entry Time
attribute enabled (see page 31).
Alarm Response
Note:
This is available only for a part set. The response for a full set is always Siren +
Comms.
Internal
Keypads and loudspeakers.
Siren
External sirens, keypads and loudspeakers.
Siren + Comms
Communication, external sirens, keypads and loudspeakers.
Note that any Siren Delay (see page 46) applies to Siren+Comms, but not Internal or
Siren alarm responses.
Siren Delay
You can use this option to delay the sounding of a confirmed alarm.
If
System Options
– Confirmation – Sounder On
is set to Confirm (see page 54),
Siren
Delay
delays the sound at keypads and loudspeakers for the specified period after the
confirmed alarm.
If
System Options
– Confirmation – Siren On
is set to Confirm (see page 55),
Siren Delay
delays the sound at the external siren for the specified period after the confirmed alarm.
The system then operates the siren and sounders for the programmed
Siren Time
. See
also "Sounder and siren operation" on page 54.
Note:
Siren Delay
has no effect if
Alarm Response
(page 46) is not set to Siren + Comms,
or if a line fault is detected.
Siren Time
This option changes the length of time that the system operates the siren and
loudspeakers during an alarm.
Note:
To comply with EN50131-1 Clause 8.6, the minimum is 90s, and the maximum is
15mins.
Pt.set Final Exit
Note:
This is available only for a part set. This option controls how the system uses Final
Exit zones when the system is part set.