Appendix C—Ratings, Cooling and Power Losses—Inline
S801+ Soft Starter
MN03900002E—November 2012
www.eaton.com
43
Power Losses
The following table lists the maximum power loss for each
S801+ Soft Starter when it is operating in bypass at the
maximum frame size current. These losses should be used in
conjunction with the losses of another cabinet mounted
device to determine the enclosure size and any cooling
requirements.
Maximum Power Loss
Catalog
Number
FLA Current
Range Inline
Power Loss
(Watts)
S801+N37…
11–37 amps
30
S801+N66…
20–66 amps
33
S801+R10…
32–105 amps
47
S801+R13…
42–135 amps
55
S801+T18…
56–180 amps
37
S801+T24…
75–240 amps
40
S801+T30…
95–304 amps
45
S801+U36…
112–360 amps
76
S801+U42…
131–420 amps
92
S801+U50…
156–500 amps
116
S801+V36…
112–360 amps
56
S801+V42…
131–420 amps
64
S801+V50…
156–500 amps
78
S801+V65…
203–650 amps
109
S801+V72…
225–720 amps
127
S801+V85…
265–850 amps
164
S801+V10…
312–1000 amps
215