Line and Load Power Wiring, S801+T…, S801+U…, and S801+V…
Notes
2
CSA approved 350–500 MCM.
3
Requires special lug cover.
Note:
S801+T…, S801+U…, and S801+V… units are
supplied standard without lugs. One kit consists of
required hardware to make connections for three (3)
phases on either line or load side of the soft starter.
Catalog
Number
Conductor
Size
Number of
Conductors
Torque
Lb-in (Nm)
Lug Kit
Kits
Required
S801+T…
4–1/0 MCM
2
250 (28.3)
EML22
2
4/0–500 MCM
1
250 (28.3)
EML23
4/0–500 MCM
2
2
250 (28.3)
EML24
2/0–300 MCM
1
225 (25.5)
EML25
2/0–300 MCM
2
225 (25.5)
EML26
S801+U…
4–1/0 MCM
2
250 (28.3)
EML22
2
4/0–500 MCM
1
250 (28.3)
EML23
4/0–500 MCM
2
2
250 (28.3)
EML24
2/0–300 MCM
1
225 (25.5)
EML25
2/0–300 MCM
2
225 (25.5)
EML26
S801+V…
4/0–500 MCM
2
2
250 (28.3)
EML28
2
4/0–500 MCM
4
2
250 (28.3)
EML30
4/0–500 MCM
6
23
250 (28.3)
EML32
2/0–300 MCM
4
225 (25.5)
EML33
Summary of Contents for S801+ Series
Page 1: ...S801 Soft Starter User Manual Effective November 2012 New Information...
Page 11: ...S801 Soft Starter x S801 Soft Starter MN03900002E November 2012 www eaton com...
Page 65: ...General Information 54 S801 Soft Starter MN03900002E November 2012 www eaton com...
Page 66: ...General Information S801 Soft Starter MN03900002E November 2012 www eaton com 55...
Page 67: ...General Information 56 S801 Soft Starter MN03900002E November 2012 www eaton com...