S801+ Operating Configuration
S801+ Soft Starter
MN03900002E—November 2012
www.eaton.com
27
Initial Configuration:
1.
It is suggested that the S801+ Soft Starter be configured
before applying the line voltage. Before applying the Line
voltage, apply 24 Vdc to the Supply connections of the
S801+’s control terminal block.
2.
Set the Operating Parameters to the desired values.
These settings assume the motor has a 1.15 Service
Factor.
Operating Parameters—Soft Start Configuration—S801+ …N3S Standard
Soft Start Config
Line Connected Motor
Units
Minimum
Maximum
Default
Notes
Overld Trip FLA
S801+N37…
Amps
11
37
11
Motor FLA parameter must be set to motor
nameplate FLA to achieve proper overload
protection
S801+N66…
Amps
20
66
20
S801+R10…
Amps
32
105
32
S801+R13…
Amps
42
135
42
S801+T18…
Amps
56
180
56
S801+T24…
Amps
75
240
75
S801+T30…
Amps
95
304
95
S801+U36…
Amps
112
360
112
S801+U42…
Amps
131
420
131
S801+U50…
Amps
156
500
156
S801+V36…
Amps
112
360
112
S801+V42…
Amps
131
420
131
S801+V50…
Amps
156
500
156
S801+V65…
Amps
203
650
203
S801+V72…
Amps
225
720
225
S801+V85…
Amps
265
850
265
S801+V10…
Amps
312
1000
312
Overload
On
Disable
On
Jam
On
Disable
On
Stall
On
Disable
On
Phase Loss
On
Disable
On
Phase Reversal
On
Disable
On
Reset Mode
Manual
Auto
Manual
Ramp Start/Current Limit
Ramp
Current
Ramp
Kick Start Torque
%
0
85
0
Kick Start Time
Seconds
0
2
0
Initial Torque
%
0
85
45
Ramp Time
Seconds
0.5
180
20
Ovrld Trip Class
5
30
20
Soft Stop Time
Seconds
0
60
0
Summary of Contents for S801+ Series
Page 1: ...S801 Soft Starter User Manual Effective November 2012 New Information...
Page 11: ...S801 Soft Starter x S801 Soft Starter MN03900002E November 2012 www eaton com...
Page 65: ...General Information 54 S801 Soft Starter MN03900002E November 2012 www eaton com...
Page 66: ...General Information S801 Soft Starter MN03900002E November 2012 www eaton com 55...
Page 67: ...General Information 56 S801 Soft Starter MN03900002E November 2012 www eaton com...