Protections
Fault Codes
To obtain the fault flash codes from the CIM, hold the RESET
button (located below the CIM) down or apply 24 Vdc to
terminal 4 and count the number of times all the LEDs on the
CIM flash.
For example, if you see three flashes, and then two more
flashes after a short pause, the flash code is 32.
The CIM can provide multiple flash codes, if more than one
error condition caused a stop. Once you see the same flash
code repeated, you have seen all the flash codes for the error
conditions that caused the stop.
For example, if you see three flashes, a pause, then two
flashes, a slightly longer pause, then four flashes, a pause,
then one flash, the flash codes are 32 and 41.
If you then see three flashes, a pause, then two flashes, you
are seeing the first code again. This means you have seen all
the flash codes for this stop.
You may now release the RESET button or remove 24 Vdc
from Control terminal Block Terminal 4.
Note:
If an overload trip has occurred, 24 Vdc power must
be applied to allow the overload thermal memory to
reset. Depending on the overload history prior to the
latest trip, this may be as long as 9 minutes.
A list of flash codes and the faults they represent is shown
below.
Fault Codes
Fault Code
Fault
11
Thermal Overload
12
Motor Stall (LED)
13
Motor Jam (LED)
14
Phase Reversal (LED)
15
Pole Over temperature
16
SCR Failed to fire
22
Phase loss (LED)
23
Internal bypass contactor dropout
24
SCR/Contactor overcurrent
25
Phase imbalance
26
Non-volatile memory error
31
Zero voltage cross failure
32
Shorted SCR, Phase loss, Load disconnect
33
Load disconnect
34
SCR instantaneous overcurrent
41
24V power supply low
42
Timer system fault
43
Watchdog reset occurred
44
PLL (DSP) fault
45
Illegal address (DSP)
Summary of Contents for S801+ Series
Page 1: ...S801 Soft Starter User Manual Effective November 2012 New Information...
Page 11: ...S801 Soft Starter x S801 Soft Starter MN03900002E November 2012 www eaton com...
Page 65: ...General Information 54 S801 Soft Starter MN03900002E November 2012 www eaton com...
Page 66: ...General Information S801 Soft Starter MN03900002E November 2012 www eaton com 55...
Page 67: ...General Information 56 S801 Soft Starter MN03900002E November 2012 www eaton com...