Electrical:
Operating voltage Ub
24 DC (16….30 V DC)
Rated current IN
Fix; 2, 4, 6, 8, 10A
Current switch-off
(in case of overload or short circuit)
Typically 1.3 x I
N
with active current limitation to
1.2 x l
N
Switch-off times for
electronic switch-off
see time / current table
Capacitive loads
Up to 20,000μF
Inductive loads
I
n
≤ 6A … τ
max
≤ 60ms
6A < I
n
≤ 10A … τ
max
≤ 12ms
10A < I
n
≤ 16A … τ
max
≤ 7,5ms
Mechanical:
Number of channels
1
Width
17.5 (1 HP)
Height
92.5mm
Depth
119.2mm
Input terminals (optional)
3 x LINE (+) and 3 x GND (-)
Output terminals
3 x LOAD (+) and 3 x GND (-)
Terminal type
Push-in terminals
Terminal capacity
2.5mm² (flexible with ferrule)
4mm² (rigid)
Busbar
LINE (+) and GND (-); max. 80A
In different lengths up to 1m
Assembly
Snap-fit onto the TH35 mounting rail (EN 60715)
Status LED
Two-colored; Green = OK; Red = Tripped
Off = channel not in operation
Slide switch
On/Off/Reset
Text field
17.5 x 6mm
Degree of protection
IP 20
Ambient temperature
-30°C to 55°C
Storage temperature
-40°C to 100°C
Switch-off times:
Rated
Current
Switch-off time
(typically)
active current
limitation
I
N
2A
460ms
1.2 x I
N
4A
240ms
1.2 x I
N
6A
160ms
1.2 x I
N
8A
108ms
1.2 x I
N
10A
108ms
1.2 x I
N
13A
75ms
1.2 x I
N
16A
75ms
1.2 x I
N